  • Page 1: Installation Manual

    INSTALLATION MANUAL Split System air conditioners RP71L7V1 RP100L7V1 RP71L7W1 RP100L7W1 RP125L7W1 RYP71L7V1 RYP100L7V1 RYP71L7W1 RYP100L7W1 RYP125L7W1...
  • Page 2 B 2 B 2 D 2 D 2 D 2 D 2 L 1 L 1 B 1 B 1 L 2 L 2 D 1 D 1 B 2 B 2 D 2 D 2 D 2 D 2 L 1 L 1 B 1 B 1 L 2 L 2...
  • Page 3 NOTES...
  • Page 4 ™ËÌ›ˆÛË Nota tal como estabelecido no Ficheiro Técnico de Construção DAIKIN.TCF.016 e com o parecer positivo de KEMA de acordo com o Certificado 81728-KRQ/ECM98-4341 . Bemærk som anført i den Tekniske Konstruktionsfil DAIKIN.TCF.016 og positivt vurderet af KEMA i henhold til Certifikat 81728-KRQ/ECM98-4341 .
  • Page 5: Table Of Contents

    OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY Insufficient strength may result in the fall of equipment TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE and causing injury. SPECIFICALLY DESIGNED FOR USE WITH THE Carry out the specified installation work in consideration EQUIPMENT AND HAVE THEM INSTALLED BY A of strong winds, typhoons, or earthquakes.
  • Page 6: Before Installation

    EFORE INSTALLATION CAUTION Ground the air conditioner. Precautions for R-407C Grounding resistance should be according to national regulations The refrigerant requires strict cautions for keeping the system Do not connect the earth wire to gas or clean, dry and tight. water pipes, lightning...
  • Page 7: Precautions On Installation

    When installing the unit in a place exposed to strong wind, pay RECAUTIONS ON INSTALLATION special attention to the following. Check the strength and level of the installation ground so that Strong winds of 5 m/sec or more blowing against the outdoor the unit will not cause any operating vibration or noise after unit's air outlet causes short circuit (suction of discharge air), installation.
  • Page 8: Installation Servicing Space

    In case of installing multiple units (2 units or more) in lateral NSTALLATION SERVICING SPACE connection per row. The numerical figures used in here represent the dimensions for the 71-100-125 class models. Figures between ( ) indicate the dimensions for the 100-125 class models. (Unit: mm) (Refer to "Precautions on installation"...
  • Page 9: Precautions On Refrigerant Piping

    Allowable pipe length and height difference Precautions to be taken. (For details, refer to the manual attached to branch piping kit.) See the table below concerning lengths and heights. Refer to figures Install the branch pipes horizontally. (Maximum inclination: 2~4. Assume that the longest line in the figure corresponds with the 20°...
  • Page 10: Precautions When Connecting Field Piping And Regarding Insulation

    Preventing foreign objects from entering Cautions for handling the valve cover Plug the pipe through-holes with putty or insulating material The valve cover is sealed where indicated by the arrow. (procured locally) to stop up all gaps, as shown in the figure. Refer to the figure.
  • Page 11: Evacuating

    Cautions for flare connection VACUATING Please refer to the table for the dimensions for processing flares Do not purge the air with refrigerants. Use a vacuum pump to and for the tightening torques. (Too much tightening will end up vacuum the installation. No additional refrigerant is provided for in splitting of the flare.) air purging.
  • Page 12: Charging Refrigerant

    HARGING REFRIGERANT Example 1 L2=7 (Ø9.5) Precaution for servicing 71 type L1=35 (Ø9.5) indoor 100 type When performing service on the unit requiring the L3=5 (Ø6.4) refrigerant system to be opened, refrigerant must be 35 type outdoor heat pump evacuated according to local regulations. G1=L1+L2=35+7=42 m G2=L3=5 This unit requires additional charging of refrigerant according to the...
  • Page 13: Electrical Wiring Work

    Precaution for pumping-down operation Precautions on electrical wiring work The outdoor unit is equipped with a low-pressure switch to protect the Before obtaining access to terminal devices, all supply circuits compressor. must be interrupted. Use only copper wires. Never short-circuit the low pressure switch in this The wiring between the indoor unit and outdoor unit must be for operation.
  • Page 14: Test Operation

    Specifications of standard wiring components When cables are routed from the unit, a protection sleeve for the conduits (PG-insertions) can be inserted at the knock-out hole. (See figure 6) Power supply Wire Wire type of wiring Bush Field between Model fuse Wire type Size...
  • Page 15: Disposal Requirements

    Precautions regarding test-runs OTES If the remote control shows E0, E3 or E4 as an error code, there is a possibility that either the shut-off valve is closed, or the outlet vent is closed. For reverse or missing phase, U1 will be displayed on the remote control for the indoor unit, and operation will be impossible.
  • Page 16: Wiring Diagram

    IRING DIAGRAM : Field wiring : Black : Live : Blue : Neutral : Orange : Terminal : Red : Connector : White : Wire clamp : Yellow : Do not operate the unit by short-circuiting S1PL. : Protective earth (screw) This would cause compressor failure.