SPECIFICATIONS − THREE PHASE
General
Data
Connections
(sweat)
1
Refrigerant (R−410A) furnished
Outdoor
Coil
Outdoor
Fan
Shipping Data − kg (lbs.) 1 package
Electrical Data
Compressor
Outdoor
Fan Motor
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Refrigerant charge sufficient for 4.6 m (15 ft.) length of refrigerant lines.
2
Heating Air Conditioning and Refrigeration type circuit breaker or fuse.
3
Refer to local codes to determine wire, fuse and disconnect size requirements.
OPTIONAL ACCESSORIES
For update−to−date information, see any of the following publications:
S
Lennox TPA*S4 Engineering Handbook
S
Lennox Commercial Price Book
Nominal kW
Liquid line o.d. − in.
Vapor line o.d. − in.
Net face area
2
m
(sq. ft.)
Tube diameter − in.
Number of rows
Fins per meter (inch)
Diameter − mm (in.)
Number of blades
Motor W (hp)
Line voltage data − 50 hz − 3ph
2
Maximum overcurrent protection (amps)
3
Minimum circuit ampacity
Rated load amps
Locked rotor amps
Power factor
Full load amps
Locked rotor amps
Model No.
TPA036S4
10.5
3/8
7/8
2.86 (6 lbs. 5 oz.)
Outer coil
1.41 (15.21)
Inner coil
1.44 (15.50)
5/16
2
866 (22)
457 (18)
4
125 (1/6)
L/s (Cfm)
965 (2042)
Rev / min
917
Watts
158
82 (180)
380 / 420V
10
8.0
6.0
46.0
0.55
1.1
1.9
Page 3
TPA048S4
TPA060S4
14.0
3/8
7/8
5.30 (11 lbs. 11 oz.)
6.24 (13 lbs. 12 oz.)
1.96 (21.11)
2.28 (24.50)
1.98 (21.31)
2.19 (23.56)
5/16
2
866 (22)
866 (22)
559 (22)
559 (22)
4
250 (1/3)
185 (1/4)
1530 (3242)
1505 (3192)
904
313
113 (250)
116 (255)
380 / 420V
380 / 420V
10
8.6
6.1
43.0
1.0
2.2
4.1
17.6
3/8
1−1/8
5/16
2
4
692
275
15
10.7
7.8
51.5
1.0
2.3
3.1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

T?class tpa036s4T?class tpa048s4T?class tpa060s4

Table of Contents