Segment Alert And System Status Codes; Reconfiguring Outdoor Control Using Icomfortt Thermostat - Lennox Signature XP21 Series Installation And Service Procedure

Heat pump lennox signature xp21 series
Table of Contents

Advertisement

Fan RPM
Model Number
Profile
0
XC/XP17−024
1
XC/XP17−030
2
Not assigned
3
Not assigned
4
XC/XP17−036 and −042
5
Not assigned
6
XC/XP17−048 and −060
7
Not assigned
8
Not assigned
9
Not assigned
10
XP21−024
11
XC21−024
12
XC/XP21−036
13
Not assigned
14
XC21−048, − 060 and
XP21−048
15
XP21−060
Seven−Segment Alert and System Status
Codes
Alert codes are displayed using the seven−segment display
located on the outdoor control.
NOTE
System fault and lockout alarm code displays
takes precedence over system status (cooling, heating
stages or defrost/dehumidification).
The seven−segment will display an abnormal condition (er-
ror code) when detected in the system. A list of the codes
are shown in table 19.
RESETTING ALERT CODES
Alert codes can be reset manually or automatically:
4. Manual Reset
Manual reset can be achieved by one of the following
methods:
S
Disconnecting R wire from the main control's R ter-
minal.
Table 18. Fan RPM Profiles
Stage 1
Stage 1
PWM %
RPM
55
400
62
450
69
500
71
550
83
600
90
650
92
675
97
700
48
350
55
400
58
425
65
475
72
525
79
575
83
600
86
625
5. Automatic Reset
Reconfiguring Outdoor Control using
icomfortt Thermostat
If any component of the HVAC system has been changed,
e.g. replacing an outdoor sensor, reconfiguring the system
will be required. To begin reconfiguring a system, press the
setup tab. Note: Even though its in a communicating sys-
tem, the fan profile will need to be set because the
icomfortt thermostat does not know what the profile
should be.
Refer to the icomfortt Thermostat Installer Setup Guide
for configuration procedures.
Page 51
Stage 2
Stage 2
PWM %
RPM
55
400
62
450
69
500
76
550
83
600
90
650
92
675
97
700
55
400
62
450
69
500
76
550
83
600
90
650
92
675
97
700
S
Turning the indoor unit off and back on again
After power up all existing codes are cleared.
After an alert is detected, the main control continues to
monitor the unit's system and compressor operations.
When/if conditions return to normal, the alert code is
turned off automatically.
EDA Stage
EDA Stage
PWM %
RPM
55
400
62
450
69
500
71
550
83
600
90
650
92
675
97
700
27
200
27
200
27
200
27
200
30
225
30
225
30
225
30
225
XP21