6. REFRIGERANT FLOW DIAGRAM

Indoor Unit
SAP – K91GJA ( 2)
Outdoor Unit
SAP – CM1621GA
Indoor Unit A
Indoor Unit B
Insulation of Refrigerant Tubing
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of condensa-
tion, both tubes must be well insulated with a proper insula-
tion material. The thickness of the insulation should be a min.
8 mm.
CAUTION
SAP – K91GJA ( 2)
SAP – CM1821GA
Wide tube
O.D.
ø9.52mm
(3/8 ")
Narrow tube
O.D.
ø6.35 mm
(1/4")
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
SAP – K91GJA ( 2)
SAP – CM1821JA
Outdoor Unit
A
B
Accumulator
Wide tube
service
valve
Narrow tube
service
valve
B
Capillary tube
A
Thickness:
Min. 8 mm
Wide tube
19
Accumulator
Insulation
Thickness:
Min. 8 mm
Narrow tube