Sanyo SAP–K91GJA (?2) Technical & Service Manual page 25

Multi-split system air conditioner
Table of Contents

Advertisement

Indoor Unit
SAP – K91GJA ( 1)
Outdoor Unit
SAP – CM1821GA
Performance at
Rating Conditions
Full Load Conditions Running Amps.
Rating Conditions
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Indoor Unit
SAP – K91GA ( 2)
Outdoor Unit
SAP – CM1821GA
Performance at
Rating Conditions
Full Load Conditions Running Amps.
Rating Conditions
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Indoor Unit
Running Amps.
A
Power Input
kW
A
Power Input
kW
: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit
Running Amps.
A
Power Input
kW
A
Power Input
kW
: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Outdoor Air Temperature 43°C D.B.
Fan Motor
Fan Motor
230V Single phase 50Hz
0.18
0.49
0.037
0.112
0.18
0.49
0.037
0.112
Fan Motor
Fan Motor
230V Single phase 50Hz
0.36
0.49
0.074
0.112
0.36
0.49
0.074
0.112
21
Outdoor Unit
Compressor
4.13
0.851
5.03
1.041
Outdoor Unit
Compressor
7.65
1.694
9.95
2.204
Complete Unit
4.8
1.00
5.7
1.19
Complete Unit
8.5
1.88
10.8
2.39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sap–cm1621gaSap–cm1821gaSap–cm1821ja

Table of Contents