Dealer Maintenance - Thermo Pride OME-72D36 Installation And Service Manual

Oil-fired furnace down flow & direct vent (sealed combustion)
Hide thumbs Also See for OME-72D36:
Table of Contents

Advertisement

All installations and services must be performed by qualified service personnel.
THIS SECTION IS ONLY TO BE PERFORMED BY TRAINED, QUALIFIED SERVICE
PERSONNEL, AND NOT BY THE FURNACE OWNER.
A. TROUBLESHOOTING
Note: Check diagnostic code through view port prior to removing doors.
When testing electrical equipment, always follow standard electrical procedures
:
and precautions.
1. Check for line voltage (110-120VAC) to the furnace. If there is no line voltage applied to
the furnace, check that disconnecting switch is "on", fuses or circuit breakers have not
blown or tripped.
2. Make sure thermostat is "calling for heat".
3. Check for adequate fuel supply and pressure. Are all the fuel shutoff valves are open?
V. DEALER MAINTENANCE
33