Positioning; Vane Auto Mode; Dew Prevention; Swing Mode - Mitsubishi Electric MSZ-G09SV Service Manual

Wireless type split-type, heat pump air conditioners
Hide thumbs Also See for MSZ-G09SV:
Table of Contents

Advertisement

(3) Positioning

The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle.
Confirming of standard position is performed in case of follows.
(a) When the OPERATE/STOP(ON/OFF) button is pressed.
(b) When the vane control is changed AUTO to MANUAL.
(c) When the SWING is finished.
(d) When the test run starts.
(e) When the power supply turns ON.
(4) VANE AUTO (
) mode
In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum
room-temperature distribution.
(1) In COOL and DRY operation
(2) In HEAT operation

(5) Dew prevention

During COOL or DRY operation with the vane angle at Angle 4 or 5 when the compressor cumulative operation time
exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention.

(6) SWING MODE (

)
By pressing the SWING button, vertical vane swings horizontally. The remote controller displays "
SWING MODE is cancelled when any of the following operations are performed.
The unit is turned off.
The vertical vane will return to the position just before the swing operation was started.
The operation mode(AUTO, COOL, DRY or HEAT)is changed.
The vertical vane will return to the position just before the swing operation was started.
The SWING button is pressed.
The vertical vane stops at the position when the button is pressed.
(7) Horizontal AIR FLOW (
The vertical vane angle changes as follows by pressing the SWING button.
Press the SWING button.
The vertical vane begins SWING.
When the vertical vane moved to the desired position, press the SWING button again.
The vertical vane stop SWING.
(8) Cold air prevention in HEAT operation.
When any of the following conditions occurs in HEAT operation, the vane angle changes to Angle 1 automatically to pre-
vent cold air blowing on users.
Compressor is not operating.
Defrosting is performed.
Indoor coil thermistor RT12 reads 24: or below.
Indoor coil thermistor RT12 temperature is raising from 24°C or below, but it does not exceed 28:.
Indoor coil thermistor RT12 temperature
NOTE: If the temperature of RT12 reads from 24: to 28: at the air conditioner starting, this control works.
)
Horizontal AIR FLOW blowing range
Cold Air Prevention
Vane angle is fixed to Angle 1.
Vane angle is fixed to Angle 4.
About 100-
COOL and DRY
About 150-
HEAT
Released
24:
41
".
Horizontal vane
Set position
Angle 1
28: