INSTALLATION

SAFETY NOTICE :

Improper installation may result in a house fire. Follow installation directions. Installation must
be in accordance with local building codes and with current CAN/CGA B149.1 & B149.2
installation codes for gas appliances.
INSTALLATION SHOULD BE DONE BY A QUALIFIED INSTALLER.
THIS GAS FIREPLACE MUST BE VENTED OUTSIDE.
The gas stove must be electrically grounded in accordance w ith the current CSA C22.1 Canadian
Electrical Code.

POSITIONING THE STOVE :

Always locate the stove as near as possible to an outside wall to keep vent length to a minimum.
Provide adequate accessibility clearances for servicing and proper operation. Never install the
stove in a hallway or near a staircase since it may block the way in case of a fire.

VENT TERMINAL LOCATION :

Your Ultra Flame stove vents through a vent terminal installed on the roof or on the outside of
any exterior wall of your house. Many restrictions apply to the vent terminal location that should
be considered before locating your stove.
The following drawing presents a summary of most of these restrictions.