(1) Data given is least negative pressure required f or pressure sw itch to close.
(2) Data given is least negative pressure required f or pressure sw itch to remain closed.
Note: The typical s ea level negative pressure data represents the minimum press ures expec ted. Shorter length of f lue pipe or single pipe systems
compared to dual pipe systems should show higher (greater negativ e) pressures.
TRIP POINT
COIL COVER
MODEL
PRESSURE SW ITCH
LOW FIRE HIGH FIRE
GMVC950453BX*
GMVC950704CX*
-0.10
AMVC950453BX*
AMVC950704CX*
GMVC950905DX*
GMVC951155DX*
-0.10
AMVC950905DX*
AMVC951155DX*
GCVC90704CX*
-0.37
ACVC90704CX*
GCVC90905DX*
-0.37
ACVC90905DX*
GCVC91155DX*
-0.37
Note: All ins tallations above 7,000 ft. require a pres s ure s w itch change. For ins tallations in Canada the *C VC 9 & *MVC95 furnaces are certified only to 4500 ft.
Note: Replacem ent pres s ure s w itch num ber is lis ted below high altitude kit num ber.
Note: All negative pres s ure readings are in inches of water colum n (" w .c.).