White Rodgers 1F95-1291 Installation And Operating Instructions Manual page 6

Big blue humidity universal non-programmable touchscreen thermostat with humidity/dehumidity control and automatic heat/cool changeover option
Hide thumbs Also See for 1F95-1291:
Table of Contents

Advertisement

INSTALLER/CONFIGURATION MENU
Menu
Program-
Non-Pro-
Reference
mable
gram-
Number
mable
28
28
25
(cont.)
(cont.)
(cont.)
29
29
26
30
30
27
31
31
28
32
32
29
33
33
30
34
34
31
35
35
32
36
36
33
37
37
34
38
38
35
39
39
36
1) This control can be confi gured for:
MS2 – Multi-Stage System (2 heat/2 cool)
HP1 – Heat Pump with one stage of compressor (2
heat/1 cool)
HP2 – Heat Pump with two stage compressor or two
compressor system, Gas or Electric backup; (Dual Fuel
see menu item 27) (4 heat/2 cool)
SS1 – Single Stage System (3 wire zone see wiring
diagrams.
2) GAS or Electric (ELE) fan operation. If the heating
system requires the thermostat to energize the fan, select
ELE. Select GAS if the heating system energizes the
fan on a call for heat. Note: Resetting the thermostat
switches the option to ELE.
3) O/B Terminal selection – Selects the operation of the
reversing valve (when item 1 is set to HP1 or HP2 only).
When set to "O" the changeover valve will be energized
in COOL to accommodate the majority of heat applica-
tions. If the heat pump requires the changeover valve to
energize in HEAT, select "B".
4) Programs per week – This control can be confi gured for
7 independent day or 5/1/1 day programming or nonpro-
grammable modes. Default is 7-day mode. The display
indicates "7 Days" as default. Other options "5 Days" or
"0 Days" can be selected. If "0 Days" is selected for non-
programmable mode, the step for EMR will be skipped, as
this feature will not be available in this mode.
5) Program Steps per day – This control can be confi gured
for 4 or 2 program steps per day. Default is "4 PS" and
can be toggled between 4 PS and 2 PS.
6) System Switch Confi guration (MS2/SS1) – This ther-
mostat is confi gured for Heat and Cool with Auto change-
over default (Cool-Off-Heat-Auto). It can be confi gured as
CONFIGURATION MENU
Press
Displayed
Press
Button
Factory
to select from
(Default)
listed options
dF (35)
Cd (60)
AO (80)
bP (80)
Hd (OFF)
Humidity
H1, OD
HR (OFF)
AH (OFF)
CH (OFF)
OC (o)
Change UV
Lamp (OFF)
350 Days
Change Pad
(OFF)
1000 Hrs
OFF
Change Filter
200 Hrs
Comments
or
5-50
Selects Dual Fuel setpoint (°F) with outdoor sensor available.
0-99
Selects compressor delay in seconds.
35-74
Selects Auxiliary Heat cut out temperature. This item appears if HP1 or
HP2 is selected and outdoor sensor is installed and enabled.
79-20
Selects Blower balance point. Selection of 80 disables this feature. This
item appears if HP1 or HP2 is selected and outdoor sensor is installed
and enabled.
On
Selects Humidity Display alternate with time.
-20-20
Selects Humidity Display adjustment.
-18
LO, HI
Selects Auto Humidity reduction.
H, C, A
Selects Automatic Humidifi cation.
On
Selects Cycle Humidifi er.
od, OFF
Selects Optimum Comfort or Optimum Dehumidifi cation.
On
Selects Change UV Lamp feature.
25-1975
Change UV Lamp duration days.
On
Selects Change Humidifi er Pad feature.
25-1975
Change Humidifi er Pad duration hours.
On
Selects Change Filter feature.
25-1975
Change Filter duration hours.
Heat & Cool (Cool-Off-Heat), or Heat Only (Off-Heat), or
Cool Only (Cool-Off).
When the control is in heat pump confi guration (HP1/
HP2), the system switch confi guration will have an
additional mode available namely, Emer for Emergency
Mode.
7) Energy Management Recovery (EMR) – (this step is
skipped if confi gured as non-programmable). When set
to "On" causes the thermostat to start heating or cooling
early to make the building temperature reach the program
setpoint at the time you specify.
Example: The heating program is 65°F at night and 70°
at 7 AM. If the building temperature is 65°F, the difference
is 5°F. Allowing 5 minutes per °F rise, the thermostat set-
point will change to 70° at 6:35 AM. Cooling allows more
time per °F, because it takes longer to reach temperature.
8, 9 & 10) Cycle Rate Selection – The factory default setting
is fast cycle (FA Cr) in all modes (Heat, Cool, Emer). To
change to slow cycling (SL, Cr), press touch keys
toggle between FA & SL. The cycle rates are below:
Mode
Fast rate
Heat
0.6°F
Cool
1.2°F
Emer
1.2°F
11) Select Compressor Lockout (CL) – Selecting (CL On)
will cause the thermostat to wait 5 minutes between cool-
ing cycles. This is intended to help protect the compressor
from short cycling. Some of the newer compressors have
a time delay built in and do not require this feature to be
activated in the thermostat. Your compressor manufactur-
er can tell you if this lockout feature is already present in
their system. When the thermostat compressor time delay
is activated, it will fl ash the set point for up to fi ve minutes.
or
Slow rate
1.2°F
1.7°F
1.7°F
6