Lennox SLP98UHV Installation Instructions Manual page 62

Collection gas furnace upflow / horizontal air discharge
Hide thumbs Also See for SLP98UHV:
Table of Contents

Advertisement

Troubleshooting: Heating Sequence of Operation (Continued)
RUN MODE (TWO−STAGE THERMOSTAT)
FIRST OR SECOND−STAGE CALL FOR HEAT
ALL INPUTS MONITORED (LIMIT, PRESSURE,
CALL FOR HEAT/COOL, FLAME LEVEL).
CALL FOR HEAT SATISFIED
3A
2nd Stage Heat
NO
2nd Stage
Call for Heat
satisfied?
YES
Combustion Air Inducer
switched to 70% rate speed
Adjust Indoor Blower
to appropiate speed
1st Stage Heat
NO
1st Stage
Call for Heat
satisfied?
YES
Gas valve
De−Energized
Combustion Air Inducer OFF
after 20−Second Post Purge
Indoor Blower OFF
after OFF Delay
1
OR
4
Wait for Call
Wait for Call
Two−Stage
Single−Stage
Thermostat
Thermostat
Page 62
RUN MODE (SINGLE−STAGE THERMOSTAT)
3B
ALL INPUTS MONITORED (LIMIT, PRESSURE,
CALL FOR HEAT/COOL, FLAME LEVEL).