High Altitude Information; Proper Combustion; Other Unit Adjustments - Lennox SLP98UHV Installation Instructions Manual

Collection gas furnace upflow / horizontal air discharge
Hide thumbs Also See for SLP98UHV:
Table of Contents

Advertisement

Manifold and Operating Signal Pressures in inches 0 − 7500 ft (0 − 2286 m)
SLP98
Manifold Pressure Nat Gas
Firing
Rate
Min
35%
0.4
70%
1.7
100%
3.2
NOTE − A natural to LP/propane gas changeover kit (table 28) is necessary to convert this unit. Refer to the changeover kit
installation instruction for the conversion procedure.

Proper Combustion

Furnace should operate a minimum of 15 minutes with cor-
rect manifold pressure and gas flow rate before checking
combustion. Take combustion sample beyond the flue out-
let and compare to the tables below. The maximum carbon
monoxide reading should not exceed 50 ppm.
TABLE 26
High Fire
Model Input Size
070
090
110
135
TABLE 27
Low Fire
Model Input Size
070
090
110
135

High Altitude Information

NOTE − In Canada, certification for installations at eleva-
tions over 4500 feet (1372 m) is the jurisdiction of local au-
thorities.
Manifold Pressure LP/Propane
Normal
Max
0.5
0.6
1.9
2.1
3.5
3.8
CO
%
CO
%
2
For Nat
2
For L.P.
7.6 − 8.6
9.1 − 10.1
CO
%
CO
%
2
For Nat
2
For L.P.
5.7
7.2 − 8.2
5.3 − 6.3
6.8 − 7.8
TABLE 25
Min
Normal
Max
1.2
1.5
1.8
5.1
5.5
5.9
9.5
10.0
10.5
SLP98UHV units require no manifold pressure adjust-
ments for operation at altitudes up to 10,000 feet (3048 m)
above sea level. Units installed at altitude of 7,501 to
10,000 feet (2287 to 3048m) require a pressure switch
change per table 28. Table 28 also lists conversion kit re-
quirements.
The® combustion air pressure switch is factory−set and re-
quires no adjustment.
Conversion Kit Requirements
LP/Propane
Model
Input
0 − 10,000
Size
(0 − 3048 m)
070
090
110
135

Other Unit Adjustments

Primary Limit
The primary limit is located on the heating compartment
vestibule panel. This limit is factory set and require no ad-
justment.
Flame Rollout Switches (Two)
These manually reset switches are located on the inside of
the burner box. If tripped, check for adequate combustion
air before resetting.
Page 51
Operating Pressure Signal
(Delta P)
Min
Normal
0.25
0.30
0.60
0.65
1.10
1.15
TABLE 28
High Altitude Pressure Switch Kit
Kit
0 − 7,500
(0 − 2286 m)
65W77
Not required
Max
0.35
0.70
1.20
7,501 − 10,000
(2287 − 3048m)
93W75