Limitations
These requirements reflect some of the conditions under
which the rack and its units were tested for stability and
safety.
It is the responsibility of the customer or unit
manufacturer to assure the rack and its units meet these
requirements. Failure to meet these requirements could
result in an unsafe condition.
Requirements
3-8
Appliance Coupler Outlets
The maximum load of the rack outlets for the Power
Control Compartment is:
Countries
Amps
EMEA
10 (IEC3 320)
USA and AG, AjPG 15 (ULjCSA)
Center-of-Gravity for A Slide-Mounted Unit
The center-of-gravity for an extended unit cannot
exceed 362 mm (14.25 in.) from the face of the rack.
If an extended system unit exceeds this distance, the
configured rack may be unstable.
If you have a rack configuration that exceeds this
center-of-gravity limit, you should test the configuration
for stability to make sure it meets ULI jCSA2
requirements, or the requirements stipulated by the
national test-house for your country.