Multi position package heat pump units with r410a (43 pages)
Summary of Contents for Goodman SSZ 16 SEER
Page 1
Refer to the appropriate Parts Catalog for part number information. • Models listed on page 3. This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does RT6214002r10 not assume any responsibility for property damage or personal injury due to improper service February 2014 procedures or services performed by an unqualified person.
Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Installation and repair of this unit Goodman will not be responsible WARNING WARNING WARNING...
Page 3
WARNING that is not design certified by damage, personal injury, or death, Goodman for use with this unit. do not store combustible materials or use gasoline or Serious property damage, personal injury, reduced unit other flammable liquids or vapors in the vicinity of this performance and/or hazardous conditions may result appliance.
PRODUCT DESIGN SSZ16 models are available in 2, 3, 4 and 5 ton sizes and These clearances will help avoid air recirculation. If installing two or more units at the same location, allow at least 24 use R-410A refrigerant. They are designed for 208/230 volt inches between units.
HEATING SPECIFICATIONS SSZ160241A* / CA*F3636*6A*+TXV/ MBE1600**-1 SSZ160361A* / CA*F4860*6A*+TXV/ MBE2000**-1 Conditions: 875 CFM @ 70°F Indoor Air Conditions: 1200 CFM @ 70°F Indoor Air Basic Unit without Capacity of Unit Basic Unit without Capacity of Unit Outdoor Outdoor Auxiliary Heat With KW of Auxiliary heat Auxiliary Heat With KW of Auxiliary heat...
Page 26
HEATING SPECIFICATIONS SSZ160601B* / CA*F4860*6A*+TXV/ MBE2000**-1 SSZ160601B* / CA*F4860*6A*+TXV/ MBE2000**-1 Conditions:1200 CFM @ 70°F DB, LOW STAGE Conditions:1800 CFM @ 70°F DB, HIGH STAGE Basi c Unit without Capacity of Unit Basi c Unit without Capacity of Unit Outdoor Outdoor Auxiliary Heat With KW of Auxiliary heat Auxiliary Heat...
Page 27
PERFORMANCE DATA PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1.
Page 28
WIRING DIAGRAMS SSZ160[24]1AA-AF; SSZ160[36-48]1AA-AD HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS WARNING UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
SSZ160[60]1AA WIRING DIAGRAMS HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS WARNING UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 30
WIRING DIAGRAMS SSZ160[60]1AB/AC/AD/AE HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS WARNING UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 31
WIRING DIAGRAMS SSZ160[24]1AG, SSZ160[36-48]1AE HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS WARNING UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. LVDR 0- RV C-RV HVDR Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 32
WIRING DIAGRAMS SSZ160[60]1BA HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS WARNING UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 33
WIRING DIAGRAMS SSZ160[60]1BA HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS WARNING UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. LVDR 0-RV C-RV HVDR Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.