Alcatel-Lucent 7210 SAS-T Installation Manual page 46

Service access switch
Hide thumbs Also See for 7210 SAS-T:
Table of Contents

Advertisement

Installing Your Switch
Warning: To comply with the GR-1089-CORE, Issue 03, requirement R4-9 [31] standard for
electromagnetic compatibility and safety, all intra-building ports are specified for use with
shielded and grounded cables at both ends.
Warning: The intra-building port(s) of the equipment or sub-assembly is suitable for
connection to intrabuilding or unexposed wiring or cabling only. The intra-building port(s) of the
equipment or sub-assembly must not be metallically connected to interfaces that connect to
the Outside Plant (OSP) or its wiring. These interfaces are designed for use as intra-building
interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE, Issue 4) and require
isolation from the exposed OSP cabling. The addition of primary protectors is not sufficient
protection in order to connect these interfaces metallically to OSP wiring.
Warning: Bare conductors must be coated with an appropriate antioxidant compound before
crimp connections are made. All unplated connectors, braided strap, and bus bars must be
brought to a bright finish and then coated with an antioxidant before they are connected.
Warning: The equipment under test (EUT) is specified for DC-I power configurations. The
battery returns must remain isolated until they reach the main power bus.
Danger:
Danger:
installation.
Danger:
Danger:
OFF switch. Unplug the power cord from the power source and disconnect the cord from the
receptacle on the power supply module to remove power.
Danger:
accessible distance of the equipment. This is intended as the disconnect device.
Page 38
Only electrical service personnel should perform wiring and cabling to the system.
All power to the equipment rack or cabinet should be disconnected before the
Power cable(s) must meet your local electric code requirements.
The power supply on/standby switch is not intended to be used as the chassis ON/
An external circuit breaker no greater than 15A must be located within a readily
7210 SAS-T Installation Guide