Start-up following the operation on manual bypass

This procedure presupposes that the load is powered by the manual bypass switch:
• The inverter is switched OFF;
• The manual bypass switch Q2 is switched ON (pos. I);
• The output switch Q1 is switched OFF (Pos. 0);
• The input fuses rectifier F1, F2, F3 and battery fuses F9, F10, F11 are removed.
NOTE !
This procedure must not be used if the UPS is used as frequency converter.
1.
Insert the rectifier-input fuses F1, F2, F3 and the battery fuses F9, F10, F11 ( insert the
external battery fuses in case of external battery).
2.
Switch ON the output switch Q1 (Pos. I).
3.
Only in case it has
been
previously
activated (* present
beside
the
text
RESET
TOTAL
OFF), restore the
command total off
by
entering
the
screen:
MENU/RESET
TOTAL OFF
4.
Switch
OFF
the
maintenance