DESCRIPTION

3.1

PRINCIPAL DIAGRAM AND MAIN ELEMENTS DESCRIPTION

Fig. 3.1-1 UPS principal diagram
The Uninterruptible Power Supply System LP 33 / 10 - 20 - 30 kVA can be divided into the following
main elements:
Electronics
The UPS is designed with a microprocessor–controlled supervision and diagnostic system.
Communication between user and UPS is achieved by the front panel consisting of an LCD
screen, displaying the operation modes, the measurements and the events / alarms.
Rectifier
The rectifier converts the 3-phase mains voltage into a controlled and regulated DC-voltage, in
order to supply power to the booster, and to charge the battery through the battery-charger.
Inverter
The inverter converts the DC voltage into a three-phase AC-voltage with constant amplitude and
frequency, which is completely independent from the AC-input voltage.
Automatic Bypass
The automatic bypass consists of a static semiconductor-switch (SSR: Static Switch Relay), used
to provide an uninterrupted transfer of the load from inverter to mains when operating in On-line
mode.
If chosen the IEM mode, the SSM transfer the load from mains to inverter in case the utility fails.
Back-Feed Protection
All LP 33 UPS's are equipped with an automatic system for the protection against voltage back
feeding towards Utility, through the Bypass (Applied Standard IEC 62040-1).
This protection works automatically by opening contactor K6 (in series with the thyristors of the
static switch) and eventually K7, and acts in case of internal defects of the system, or due to wrong
manipulations on the maintenance bypass Q2.
Manual Bypass
The manual bypass consists of a pair of manual switches Q1 and Q2, which allow the isolation of
the UPS from the load, while still supplying the load with power directly from the mains.
Battery
The battery, normally stored by the battery-charger, supplies the DC energy to inverter in the
event of mains failure.
Operating Manual LP 33 / 10-20-30 kVA
OPM_LPS_33E_10K_30K_4CN_V010.doc
11/82