Panasonic S-45PU1E5 Technical Data & Service Manual page 307

Inverter r410a
Table of Contents

Advertisement

H05 Sensor failure, Compressor discharge temperature sensor (TD) disconnected
1.
Error Detection Method
(In case of outdoor temperature over 5°C) For 10 minutes since started, variation of discharge temperature is always
detected within 2°C comparing with the temperature just before starting.
(In case of outdoor temperature less than 5°C) For 30 minutes since started, variation of discharge temperature is
always detected within 2°C comparing with the temperature just before starting.
1 Sensor
1-1
Is the sensor properly installed at the holder side?
Trouble
1-2
Replace the sensor with a new one.
5-35
Yes
1-2
No
Reinstall correctly.
5