Sanyo Big PACi 18 Series Technical Data & Service Manual page 68

Big pack i dc inverter
Table of Contents

Advertisement

1-2. Major Component Specifi cations
(A) Indoor Units
Concealed-Duct Type SPW-UR484GH56 (A/B), UR484SH56B, U485H
MODEL No.
Source
Controller P.C.B. Ass'y
Fan (Number...diameter, depth)
Fan motor
Model...Nominal output
Source
No. of pole...rpm (230V, High)
Coil resistance
(Ambient temperature 20°C)
Safety device
Operation temperature
Operation temperature
Run capacitor
Electronic expansion valve
Coil
Coil resistance (at 20°C)
Valve body
Heat Exchanger
Coil
Rows...fin pitch
Face area
Panel
Model No.
Dew proof heater
Auto louver motor
Coil resistance (at 20°C)
Drain Pump
Rated
Total head & capacity
SPW-
UR484GH56 (A/B)
220 - 230 - 240V, single-phase, 50/60Hz
CR-UXRP71B-B (Microprocessor)
W
SFC4X-141A5P...160W
220 - 230 - 240V, single-phase, 50/60Hz
rpm
BRN–WHT : 25.79
WHT–VLT : 5.086
VLT–ORG : 8.626
Open °C
Close °C
VAC, µF
Aluminium plate fin / Copper tube
mm
2
m
ADP-1413
VAC, W
500mm, 400cc/min 1200mm, 400cc/min 500mm, 400cc/min
1-63
SPW-
SPW-
UR484SH56B
U485H
U485SHT
Centrifugal (3...ø190, L200)
KFC4X-141D5P-S...160W
4P...1,207
ORG–YEL : 5.792
YEL–BLK : 6.746
BLK–PNK : 6.361
130 ± 5
(115 ± 5)
450 VAC, 8.0 µF
3...2.0
0.308
ZPLD-12230ST-XH-B
AC 230V, 50Hz, 12W
1
ADP-1413