1-2. Major Component Specifi cations
(A) Indoor Units
Concealed-Duct Type SPW-UR254GH56 (A/B), UR254SH56B, U255H
MODEL No.
Source
Controller P.C.B. Ass'y
Fan (Number...diameter, depth)
Fan motor
Model...Nominal output
Source
No. of pole...rpm (230V, High)
Coil resistance
(Ambient temperature 20°C)
Safety device
Operation temperature
Operation temperature
Run capacitor
Electronic expansion valve
Coil
Coil resistance (at 20°C)
Valve body
Heat Exchanger
Coil
Rows...fin pitch
Face area
Panel
Model No.
Dew proof heater
Auto louver motor
Coil resistance (at 20°C)
Drain Pump
Rated
Total head & capacity
SPW-
UR254GH56(A/B)
220 - 230 - 240V, single-phase, 50/60Hz
CR-UXRP71B-B (Microprocessor)
W
SFG4X-71C3P...70W
220 - 230 - 240V, single-phase, 50/60Hz
rpm
BRN–WHT : 74.72
WHT–VLT : 19.14
VLT–ORG : 10.52
Open °C
Close °C
VAC, µF
Aluminium plate fin / Copper tube
mm
2
m
ADP-1413
VAC, W
500mm, 400cc/min
1-61
SPW-
SPW-
UR254SH56B
U255H
U255SHT
Centrifugal (2...ø190, L200)
KFG4X-71B5P-S...70W
4P...1,063
ORG–YEL : 9.588
YEL–BLK : 10.52
BLK–PNK : 21.72
130 ± 5
(115 ± 5)
450 VAC, 5.0 µF
3...1.5
0.189
ZPLD-12230ST-XH-B
AC 230V, 50Hz, 12W
1200mm, 400cc/min 500mm, 400cc/min
1
ADP-1413