Start- -Up, Adjustment, And Safety Check; Step 1 -General; Step 2 -Start- -Up Procedures - Payne PG8J Installation Instructions Manual

Single-stage deluxe induced-combustion 4-way multipoise furnace
Table of Contents

Advertisement

START- - UP, ADJUSTMENT, AND SAFETY
CHECK
Step 1 —General
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
This furnace is equipped with manual reset limit switches in
the gas control area. The switches open and shut off power
to the gas valve if a flame rollout or overheating condition
occurs in the gas control area. DO NOT bypass the
switches. Correct inadequate combustion air supply
problem before resetting the switches.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs.
Use care and wear appropriate protective clothing, safety
glasses, and gloves when handling parts and servicing
furnaces.
1. Maintain 115- -v wiring and ground. Improper polarity will
result in rapid flashing LED and no furnace operation.
2. Make thermostat wire connections at the 24- -v terminal
block on the furnace control. Failure to make proper con-
nections will result in improper operation. (See Fig. 26.)
3. Gas supply pressure to the furnace must be greater than
4.5- -in. wc (0.16 psig ) but not exceed 14- -in. wc (0.5
psig).
4. Check all manual- -reset switches for continuity.
5. Install blower compartment door. Door must be in place to
operate furnace.
6. Replace outer door.
Step 2 —Start- -Up Procedures
WARNING
!
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and or property damage.
Never purge a gas line into a combustion chamber. Never
use matches, candles, flame, or other sources of ignition for
the purpose of checking leakage. Use a soap- -and- -water
solution to check for leakage.
1. Purge gas lines after all connections have been made.
2. Check gas lines for leaks.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury, or death.
Blower access door switch opens 115- -v power to control.
No component operation can occur unless switch is closed.
Caution must be taken when manually closing this switch
for service purposes.
3. To Begin Component Self- -Test: Remove blower access
door. Disconnect the thermostat R lead from the furnace
control board. Manually close the blower door switch.
Short (jumper) the COM- -24v terminal on control to the
TEST/TWIN 3/16- -inch quick connect terminal on control
until LED goes out (approximately 2 sec). Gas valve and
humidifier will not be turned on. (See Fig. 25.)
NOTE: The furnace control allows all components, except the
gas valve, to be run for short period of time. This feature helps
diagnose a system problem in case of a component failure.
Component test feature will not operate if any thermostat signal is
present at the control.
Component test sequence is as follows:
Refer to service label attached to furnace or see Fig. 50.
a. LED will display previous status code 4 times.
b. Inducer motor starts and continues to run until Step f
of component test sequence.
c. Hot surface igniter is energized for 15 sec., then off.
d. Blower motor operates on HEAT speed for 10 sec.
e. Blower motor operates on COOL speed for 10 sec.
f. Inducer motor stops.
g. Reconnect R lead to furnace control board, release
blower door switch and re- -install blower door.
4. Operate furnace per instruction on door.
5. Verify furnace shut down by lowering thermostat setting
below room temperature.
6. Verify furnace restarts by raising thermostat setting above
room temperature.
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pg8m

Table of Contents