Viessmann Vitorond 200 VD2 Series Technical Data Manual page 9

Triple-pass hot water heating boiler 1255 to 4387 mbh (368 to 1285 kw)
Hide thumbs Also See for Vitorond 200 VD2 Series:
Table of Contents

Advertisement

Vitorond 200, VD2 Series 320 to 1080 Technical Data
Technical Data
(continued)
Boiler supply header
Boiler return header
Legend
TCP
Additional temperature control port ½ in.
AQW Aquastat well tapping ½ in.
BWR Boiler water return
BWS Boiler water supply
ACP
Additional control port ½ in. (pressure gage)
S
Return temperature sensor port
1
S
Boiler pump temperature sensor ½ in.
2
RWE Return water elevation 2½ in.
SR
Safety return - connection to precharged membrane
expansion tank
SS
Safety supply - connection to pressure relief valve
Boiler Connection Kit (Standard Equipment)
consisting of boiler supply and return header
Low temperature protection
Low temperature protection packages from Viessmann
are required for Rondomat boilers. A 30% Boiler Flow
Package is typically utilized in single-boiler installations.
100% Boiler Flow Packages are utilized in single- and
multiple-boiler installations.
Selection of the correct package depends on the
characteristics of the heating system, and the degree
of control necessary to protect the boiler. Contact
Viessmann for assistance.
Product Information
9