Viessmann Vitorond 200 VD2 Series Technical Data Manual page 7

Triple-pass hot water heating boiler 1255 to 4387 mbh (368 to 1285 kw)
Hide thumbs Also See for Vitorond 200 VD2 Series:
Table of Contents

Advertisement

Vitorond 200, VD2 Series 320 to 1080 Technical Data
Technical Data
(continued)
Technical Data
Boiler Model
VD2-
Boiler connections
Boiler supply
in.
and return
Safety supply
*5
in.
Safety return
*5
in.
Drain valve
in.
Heating surface area
Flue gas side
ft
2
(m
2
)
Water side
ft
2
(m
2
)
*6
Flue gas
- Temperature
ºF
(gross)
*7
(ºC)
- Flue gas mass
lbs./h
flow rate
(kg/h)
With minimum heating input and a 2-stage burner (operation of stage 1)
- Temperature
ºF
(ºC)
- Flue gas mass
lbs./h
flow rate at
(kg/h)
min. input rate
Boiler standby
%
loss based on
max. heating
input and hot
water supply and
return temps. of
167 / 140°F
(75 / 60 °C)
Vent pipe collar
in.
(mm)
outer 7
*8
"w.c.
Flue gas
resistance
(mbar)
- at upper end
of rated input
Required flue
Pa
draft Category I
"w.c.
Positive pressure
Pa
"w.c.
Category III
*5
Connections for boiler connection kit (standard equipment).
*6
Combustion results are based on 13.0% CO
supply temperature of 167°F (75°C), and a system return temperature of 140°F (60°C).
*7
Measured flue gas temperature with a combustion air temperature of 68° F (20° C) and a boiler water temperature
of 176°F (80°C).
*8
Vent pipe collar diameter does not automatically indicate vent/chimney size. See page 15 for details.
The combustion burner head material must be suitable for temperatures of at least 932°F (500°C).
For information regarding other Viessmann System Technology componentry, please reference documentation
of respective product.
320
380
440
4
4
4
2b
2b
2b
2b
2b
2b
c
c
c
170
196
212
(15.8)
(18.2)
(19.7)
98
109
120b
(9.1)
(10.1)
(11.2)
374
374
374
(190)
(190)
(190)
1301
1598
1854
(590)
(725)
(841)
266
266
266
(130)
(130)
(130)
710
842
974
(322)
(382)
(442)
0.40
0.38
0.35
12
12
12
(300)
(300)
(300)
0.20
0.35
0.51
(0.5)
(0.9)
1.3)
0
0
0
(0)
(0)
(0)
20
20
20
(0.08)
(0.08)
(0.08)
with fuel oil #2 and 10% CO
2
500
560
630
4
4
4
2b
2b
2b
2b
2b
2b
c
c
c
232
254
274
(21.5)
(23.6)
(25.5)
131
142
153
(12.2)
(13.2)
(14.2)
374
374
374
(190)
(190)
(190)
2081
2337
2601
(944)
(1060)
(1180)
266
266
266
(130)
(130)
(130)
1109
1241
1398
(503)
(563)
(634)
0.32
0.31
0.29
12
12
12
(300)
(300)
(300)
0.67
0.75
0.83
(1.7)
(1.9)
(2.1)
0
0
0
(0)
(0)
(0)
20
20
20
(0.08)
(0.08)
(0.08)
2
Product Information
700
780
860
4
4
4
2b
2b
2b
2b
2b
2b
c
c
c
296
317
339
(27.5)
(29.5)
(31.5)
165
175
18.7
(15.3)
(16.3)
(17.4)
374
374
374
(190)
(190)
(190)
2897
3196
3527
(1314)
(1450)
(1600)
266
266
266
(130)
(130)
(130)
1552
1730
1907
(704)
(785)
(865)
0.28
0.27
0.26
12
12
12
(300)
(300)
(300)
1.10
1.54
1.93
(2.8)
(3.9)
(4.9)
0
0
0
(0)
(0)
(0)
20
20
20
(0.08)
(0.08)
(0.08)
with natural gas, as well as a system
950
1080
4
4
2b
2b
2b
2b
c
c
358
380
(33.3)
(35.3)
198
209
(18.4)
(19.4)
383
383
(195)
(195)
3825
4277
(1735)
(1940)
275
275
(135)
(135)
2110
2394
(957)
(1086)
0.25
0.24
12
12
(300)
(300)
1.77
2.28
(4.5)
(5.8)
0
0
(0)
(0)
20
20
(0.08)
(0.08)
7

Hide quick links: