Before running the system

Self test mode
Setting option switches and function of keys
1. Self test mode
- Self Test Mode is implemented ignoring errors .
- It can be implemented without OUTDOOR UNIT installation .
- Buttons have new functions as shown in the upper table under the Self Test Mode
2. Enter and quit Self test mode
To enter Self test mode
- Set DIP #5 (wired remote controller) "ON" and reset power.
- Press both "Set" and "Test" buttons over 3 sec .
- 'TEST' icon and sign pop up.
To quit the self test mode
- Press "Cancel " button over 3 sec .
3. How to use
- 'Not available' icon pops up when the buttons not shown in the upper table are pressed .
- All the functions' default states are "OFF"
- Pressing the button (#1~#8) makes its function "ON" and Cancel button makes all the functions "OFF"
- Back up Heater 1(button#2) and 2(button#3) are not available when the Water Pump (button #1) is not "ON"
- Every time you press the View button, it shows temperature sensor values in order . PHE water inlet
Backup Heater outlet
for 5 sec.
- 'HEAT' or 'COOL' sign and thermostat icon pop up instead of 'TEST' sign when the thermostat is connected .
Water Tank
Room. It goes back to the previous state when there is no View button input
(3sec) Enter Self Test
Mode
Function OFF / (3sec)
Quit Self Test Mode
Water Pump
Back up Heater 1
state
st
Back up Heater 2
state
st
Booster Heater
Back up Boiler
DHW Valve
Zone #1 Valve
Zone #2 Valve
Sho
ve temp sensor
values in order
Not available
Thermostat (Heating)
No 1 / No 2
Thermostat (Cooling)
No 1 / No.2
PHE water outlet
31