AIR FOR COMBUSTION AND VENTILATION
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the floor on the
wall connecting the two spaces (see options
1 and 2, Figure 2). You can also remove door
into adjoining room (see option 3, Figure 2).
Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and
Ventilation for required size of ventilation
grills or ducts.
Ventilation
Grills Into
Adjoining
Or
Room,
Remove
Option 1
Door into
Adjoining
Room,
Option
3
Figure 2 - Ventilation Air from Inside Building
NOTICE: This heater is intended for
use as supplemental heat. Use this
heater along with your primary heat-
ing system. Do not install this heater
as your primary heat source. If you
have a central heating system, you
may run system's circulating blower
while using heater. This will help cir-
culate the heat throughout the house.
In the event of a power outage, you
can use this heater as your primary
heat source.
WARNING: A qualified service
person must install heater. Follow all
local codes.
NOTICE: State or local codes may only allow
operation of this appliance in a vented con-
figuration. Check your state or local codes.
8
12"
Ventilation Grills
Into Adjoining Room,
Option 2
12"

INSTALLATION

www.SuperiorFireplaces.US.com
Continued
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two perma-
nent openings: one within 12" of the ceiling
and one within 12" of the floor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering
the attic will activate the power vent.
Outlet
Air
Inlet
Air
Figure 3 - Ventilation Air from Outdoors
Any outside air ducts and/or ash
dumps in the fireplace shall be per-
manently closed at time of appliance
installation.
WARNING: Make sure the selector
switch is in the OFF position before
installing heater.
WARNING: Seal any fresh air vents
or ash clean-out doors located on floor
or wall of fireplace. If not, drafting may
cause pilot outage or sooting. Use a
heat-resistant sealant. Do not seal
chimney flue damper.
Ventilated
Outlet
Attic
Air
Ventilated
Inlet Air
Crawl Space
To Attic
To
Crawl
Space
126816-01A