Toshiba RAV-SM562MUT-E Service Manual page 60

Split type air conditioner
Hide thumbs Also See for RAV-SM562MUT-E:
Table of Contents

Advertisement

Memorandum for setup contents (Item code table (Example))
DN
Item
01
Filter sign lighting time
02
Dirty state of filter
03
Central control address
06
Heating suction temp shift
0F
Cooling only
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor unit address
14
Group address
19
Flap type (Adjustment of air direction)
Temp difference of automatic cooling/
1E
heating selecting control points
28
Automatic reset of power failure
2A
Option
2b
Thermo output selection
2E
Option
32
Sensor selection
5d
High ceiling selection
60
Timer set (Wired remote controller)
8b
Correction of high heat feeling
Type
Item code [10]
Setup data
0014
* Initial setup value of EEPROM installed on the service P .C. board
Indoor unit capacity
Item code [11]
Setup data
0009
* Initial setup value of EEPROM installed on the service P .C. board
Memo
Type
Compact 4-way cassette
Type
Compact 4-way cassette
– 60 –
At shipment
According to type
0000: Standard
0099: Unfixed
0002: +2°C (Floor type: 0)
0000: Shared for cooling/heating
According to model type
According to capacity type
0099: Unfixed
0099: Unfixed
0099: Unfixed
According to type
0003: 3 deg (Ts ± 1.5)
0000: None
0002:
0000: Thermo ON
0000:
0000: Body sensor
0000: Standard
0000: Available
0000: None
Abbreviated name
RAV-SM562MUT-E
Abbreviated name
RAV-SM562MUT-E