Toshiba RAV-SM562MUT-E Service Manual page 50

Split type air conditioner
Hide thumbs Also See for RAV-SM562MUT-E:
Table of Contents

Advertisement

[F06 error]
Are connections of
TE/TS sensor connectors of
CDB CN604/CN605 normal?
YES
Are characteristics of TE/TS sensor
resistance values normal?
YES
®
Check CDB.
Defect
Replace
[F04 error]
Is connection of TD sensor connector
of CDB CN600 normal?
YES
Are characteristics of TD sensor
resistance value normal?
YES
®
Check control P.C. board.
Defect
Replace
[F08 error]
Is connection of TO sensor connector
of CDB CN601 normal?
YES
Are characteristics of TO sensor
resistance value normal?
YES
®
Check CDB.
Defect
Replace
NO
* (For RAV-SM562AT-E, CN600 TE sensor and CN603 TS sensor)
NO
* Refer to Characteristics-3.
NO
* (For RAV-SM562AT-E, CN601 TD sensor)
NO
* Refer to Characteristics-4.
NO
* (For RAV-SM562AT-E, CN602 TO sensor)
NO
* Refer to Characteristics-5.
– 50 –
Correct connection of connector.
Replace TE and TS sensors.
Correct connection of connector.
Replace TD sensor.
Correct connection of connector.
Replace TO sensor.