[L20 error]
Are cable connections to communication line U3, U4 normal?
Are not multiple same central
control network addresses connected?
®
Check central controller (including connection interface) indoor P.C. board.
Defect
Replace.
[L30 error]
Are outside devices of connector CN80 connected?
Do outside devices normally operate?
Check operation cause.
[P10 error]
Is connection of float switch connector
(Indoor control P.C. board CN34) normal?
Does float switch
operate?
YES
Does drain pump
operate?
YES
Check drain pipe, etc.
[F10 error]
Is connection of TA sensor connector
(indoor P.C. board CN104) normal?
Are characteristics of TA sensor resistance value normal?
YES
NO
YES
YES
NO
YES
NO
NO
Is power of drain
pump turned on?
YES
YES
* Refer to Characteristics-1.
NO
YES
NO
NO
NO
Is circuit
cabling normal?
YES
NO
YES
NO
NO
– 44 –
Correct cable connection
Correct central control network address.
®
Check indoor P.C. board (MCC-1402).
Defect
Replace
®
Check outside devices.
Defect
Replace
Correct connection of connector.
Check and correct cabling/wiring.
®
Check indoor P.C. board (MCC-1402).
Defect
Replace
®
Check indoor P.C. board (MCC-1402).
Defect
Replace
Replace drain pump.
Check cabling.
Correct connection of connector.
Replace TA sensor.
®
Check indoor P.C. board (MCC-1402).
Defect
Replace