No.
Item
14
Central control
1) Setting at the central controller side enables to select
mode selection
2) RBC-AMT31E
15
Energy-save
1) Selecting [AUTO] mode enables an energy-saving to
control
(By connected
2) The setup temperature is shifted (corrected) in the
outdoor unit)
3) Data (Input value room temp. Ta, Outside temp. To, Air
4) The setup temperature is shifted every 20 minutes,
16
Max. frequency
1) This control is operated by selecting [AUTO] opera-
cut control
2) COOL operation mode: the frequency
3) HEAT operation mode: the frequency
17
DC motor
1) When the fan operation has started, positioning of the
2) The motor operates according to the command from
NOTES :
• When the fan rotates while the air conditioner stops
• When a fan locking is found, the air conditioner stops,
Outline of specifications
the contents which can be operated on the remote
controller at indoor unit side.
[Last push priority] :
The operation contents can be selected from both
remote controller and central controller of the indoor
unit side, and the operation is performed with the
contents selected at the last.
[Center] :
Start/Stop operation only can be handled on the
remote controller at indoor unit side.
[Operation Prohibited] :
It cannot be operated on the remote controller at
indoor unit side. (Stop status is held.)
be operated.
range not to lose the comfort ability according to input
values of various sensors.
volume, Indoor heat exchanger sensor temp. Tc) for
20 minutes are taken the average to calculate
correction value of the setup temperature.
and the shifted range is as follows.
In cooling time : +1.5 to –1.0K
In heating time : –1.5 to +1.0K
tion mode.
is controlled according to the following
figure if To < 28°C.
is controlled according to the right
figure if To > 15°C.
stator and the rotor are performed.
(Moves slightly with tap sound)
the indoor controller.
due to entering of outside air, etc, the air conditioner
may operated while the fan motor stops.
and an error is displayed.
Ta(˚C)
+4
+3
Tsc
Ta(˚C)
Tsh
–3
–4
– 31 –
Remarks
(No display)
[
] goes on.
[
] goes on.
In a case of wireless type, the
display lamp does not change.
However, contents which can be
operated are same.
The status set in [
[Operation Prohibited] mode is
notified with the receiving sound
"Pi, Pi, Pi, Pi, Pi" (5 times).
Normal control
Max. frequency is restricted
to approximately the rated
cooling frequency
Max. frequency is restricted
to approximately the rated
heating frequency
Normal control
Check code [P12]
] /