Alternate Condensate Drain Piping Installation Using 1/2" Pvc Or 3/4" Cpvc - Napoleon 9600 Series Installation And Operating Instructions Manual

Two stage multi position high efficiency (condensing) forced air gas furnace
Table of Contents

Advertisement

NOTE
It is recommended that the condensate drain assembly not be cemented to the condensate trap
outlet, if removal of the condensate trap is required in the future. Use a piece of the provided 1/2"
drain hose if removal of the condensate trap is anticipated.
IMPORTANT:
IF AN AIR CoNDITIoNINg EVApoRAToR CoIl DRAIN IS To ShARE ThE FuRNACE DRAIN
lINE, IT ShoulD bE CoNNECTED WITh A TEE FITTINg DoWNSTREAm FRom ThE
TRAp. Do NoT CoNNECT ThE EVApoRAToR CoIl CoNDENSATE DRAIN upSTREAm oF
ThE FuRNACE DRAIN TRAp ASSEmbly.
11.5 alTeRnaTe ConDensaTe DRaIn pIpInG InsTallaTIon UsInG 1/2" pvC
oR 3/4" CpvC
The supplied parts bag includes a length of ½" and ⅝" rubber hose and the condensate trap. Install the con-
densate trap according to instructions included in the Installation and operating manual.
FIGURE 17
If installing with ½" pVC, use the ½" hose. If installing with ¾" CpVC, use the 5/8" hose. Slide the appropriate
hose over the condensate trap outlet and cut it flush with the end of the outlet. The remaining rubber should be
flush with the end of the outlet on the condensate trap. The remaining hose is sufficient length to accommodate
all furnace orientations.
FIGURE 19
A ½" pVC coupling or bushing will fit snug over the ½" rubber hose. A ¾" CpVC coupling or bushing will fit
snug over the 5/8" rubber hose. This method ensures a water tight seal and also allows the condensate trap to
be easily removed for service.
FIGURE 18
FIGURE 20
33
W415-0919 / D / 03.27.13