Optional Accessories (Field Supplied/Installed); Electric Air Cleaner; Power Humidifier; Emergency Heat Mode - Napoleon 9600 Series Installation And Operating Instructions Manual

Two stage multi position high efficiency (condensing) forced air gas furnace
Table of Contents

Advertisement

16.0
opTIonal aCCessoRIes (fIelD sUpplIeD/
InsTalleD)

16.1 eleCTRIC aIR CleaneR

The integrated furnace control has provisions to supply power and control an electronic air cleaner rated at
120vac, 1.0 amp max. 120 volt power will be available at these terminals whenever the
circulating fan is operating in the
NOTE
Furnace models equipped with a x-13 air circulating blower motor require a connection to the EAC
terminal on the control board. When installing an electronic air cleaner, a piggy back connector must
be used. Refer to the wiring diagram.

16.2 poWeR hUMIDIfIeR

The integrated furnace control has provisions to supply power and control a line voltage humidifier or the
primary of a 120 / 24 volt humidifier step down transformer, rated at 120vac, 1.0 amp max.
NOTE
All HUM and EAC terminals are 120v. Do not directly connect 24v equipment to these terminals.

16.3 eMeRGenCY heaT MoDe

If the ECm blower motor fails and a replacement is not available immediately, you can temporarily replace
the blower motor with a conventional fractional horsepower pSC blower motor. Connect the neutral wire to
a neutral (NEuTRAl) connection terminal on the furnace control board, and the hot (lINE) leg to the EAC
terminal. The EAC terminal is powered during any heating or cooling demand, and the blower will operate until
a new ECm motor can be obtained.
heating,
cooling, and continuous fan modes.
43
W415-0919 / D / 03.27.13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents