Gas Piping - Kenmore 153.335863 Owner's Manual

Power vent gas water heater
Table of Contents

Advertisement

Installation
Instructions
(cont'd)
Gas Piping
_,WARNING
Make sure the gas supplied is the same type listed on the
model rating plate. The inlet gaspressuremust not exceed
10.5in, water column(2.6kPa)for natural gasor 13 in. water
column (3.2kPa) for propane (L.R) gas. The minimum inlet
gas pressurelisted on the model rating plate is for the pur-
poseof input adjustment.
&WARNING
, ]
If the gascontrol valveis subjected to pressures exceeding '/2I
pound per squareinch(3.5kPa), the damageto the gascon-I
trol valvecouldresult in a fire or explosion from leakinggas. J
_,WARNING
If the main gasline shutoffservingall gasappliancesis used,
alsoturn "off" the gasat each appliance. Leaveall gasappli-
ances shutoff untilthe water heater installationiscomplete.
_,WARNING
]
Use pipe joint comp_ape
marked as being|
resistant to the actionof petroleum [Propane(LP.)] gases, j
SEDIMENT
TRAP
A sediment trap shall be installed as close to the inlet of the
water heater as practical at the time of water heater installation.
The sediment trap shall be either a tee fitting with a capped nip-
ple in the bottom outlet or other device recognized as an effec-
tive sediment trap. Ira tee fitting is used, it shall be installed in
conformance with one of the methods of installation shown
below.
Connecting the gas piping to the gas control valve of the water
heater can be accomplished by either of the two methods shown.
GAS
PIPING
WITH
FLEXIBLE
CONNECTOR
A gas line of suft]cient size _nust be run to the water heater.
Consult the latest edition of National Fuel Gas Code ANSI
Z223.1, also referred to as NFPA 54 and the gas company con-
cerning pipe size.
There must be:
• A readily accessible manual
shut off valve in the gas supply line
serving the water heater, and
• A drip leg (sediment
trap) ahead of the gas control valve to help
prevent dirt and foreign materials from entering the gas control
valve,
• A flexible gas connector
or a ground joint union between
the
shutoffvalve
and control valve to permit servicing of the unit.
Be sure to check all the gas piping
for leaks before lighting the
water heater. Use a soapy water solution,
not a match
or open
flame. Rinse offsoapy solution and wipe dry.
Standard
Models
are for installation
up to 3,300 feet above sea
level.
High Altitude
Models
are for installation
from 3,300 to 5,500
feet above sea level.
If a standard model is installed above 3,300 feet or a high altitude
model
is installed
above 5,500
feet, the input
rating must
be
reduced at the rate of 4 percent for each 1,000 feet above sea level.
Contact
your local Sears Service Center
or gas utility for further
information.
&WARNING
The appliance and its gas connection must be leak tested
beforeplacingthe appliance in operation.
AWARNING
• The appliance and its individual shutoff valve must be discon-
nected from the gasSupply piping system during any pressure
testing of the gas system at test pressures in excess of I/2
pound per square inch (3.5kPa).
• The appliance must be isolatedfrom the gas supply piping sys-
tem by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test pres-
suresequal or lessthan I/2 pound per square inch (3.5kPa).
22
MANUAL SHUT OFF
VALVE
_AS
SUPPLY PIHNG
FLEXIBLE GAS CONNECTOR
LABELED AS COMPLYING
WITH ANSI STANDARDS
LOOP
GROUND }OIN_
UNION
(OprJonal)
3" MIN.
GAS
CONTROL
VALVE
GAS
PIPING
WITH
ALL
BLACK
IRON
PIPE
TO
GAS
CONTROL
MANUAL
SHUT OFF _CA$
SUPPLY PIPING
VALVE
BLACK PIPE
GROUND
JOINT
UNION 3" MIN.
GAS
CONTROL
VALVE
&WARNING
Contaminants in the gas lines may cause improper operation
of the gas control valve that may result in fire or explosion.
Before attaching the gas line be sure that all gas pipe is clean
on the inside. To trap any dirt or foreign material
in the gas
supply line, a drip leg (sometimes
called a sediment trap)
must be incorporated in the piping. The drip leg must be
readily accessible. Install in accordance with the "Gas Piping"
section. Refer to the latest edition of the National Fuel Gas
Cede, ANSI Z223.1, also referred to as NFPA 54.