Kenmore 153.335863 Owner's Manual page 17

Power vent gas water heater
Table of Contents

Advertisement

Installation
Instructions
(cont'd)
Venting
(cont'd)
AWARNING
]
sure vent pipe is properlyconnectedto preventescapeof|
gerous flue gases whichcouldcausedeadlyasphyxiation.
]
AWARNING
Chemical vapor corrosionof the flue and vent system may
occurif air for combustioncontainscertainchemicalvapors.
Spraycan propellants,cleaningsolvents,refrigerator and air
conditioner refrigerants, swimming pool chemicals,calcium
and sodium chloride,waxes,bleach,and process chemicals are
typicalcompounds whicharepotentially corrosive.
Vertical and horizontal runs must be securely supported at 3'/2
foot intervals.
STRAPPING
VENTING
THROUGH
AN OUTSIDE
WALL
ALL MODELS
3" ABS Schedule 40 vent piping supplied in the water heater
_r
ton:
1. A 3" ABS Schedule 40-45 ° vent cap with wire screen.
2. A 3" PVC Schedule 40-90 ° street ell; used to connect the
vent pipe to the water heater when the vent pipe is to be
turned horizontally directly off the blower.
3. A 5' section of Y' PVC Schedule 40 pipe (more may be
required and must be supplied locally).
3" PVC SCHEDULE 40
90 ° ELBOW
VENT CAP
WITH
SCREEN
The water heater requires its own (separate) venting system.
1. The water heater requires its own (separate)
venting system.
2. 3" PVC, ABS or CPVC Schedule
40 piping and fittings are
acceptable
materials
for the vent system
on all 40 gallon
models and 50 gallon 40,000
BTU/HR
models.
3
It cannot be connected
to existing vent piping or chimney.
4. It must terminate
horizontally
to the outdoors.
ALL 40 GALLON
AND 50 GALLON
40,000 BTU/HR
MODELS -- OPTIONAL
2" VENT PIPING
2" PVC Schedule 40 vent piping:
1. A wire screen to fit a 2" PVC Schedule 40-45 ° vent cap is
supplied with the water heater.
2, A 2" PVC Schedule 40-45 ° vent cap (must be supplied locally).
3, A 3" PVC Schedule 40 pipe, minimum length of 3" (must
be supplied locally).
4, A 3" to 2" PVC Schedule 40 reducer (must be supplied
locally).
5, A 2" PVC Schedule 40-90 ° street ell; used to connect the
vent pipe to the reducer when the vent pipe is to be turned
horizontally off the blower (supplied locally).
6. A 2" PVC Schedule 40 pipe (must be supplied locally).
2" PVC SCHEDULE 40
90 ° ELBOW
L
2" SCHEDULE 40 PVC PIPE
[_
3" TO 2" PVC REDUCER
3" CHEDULE 40 FVC PIPE
ININUH LENGTH 3")
I
I
VENT CAP
AND
SCREEN
1. The water heater requires its own (separate)
venting system.
2. 2" and Y' PVC, ABS, or CPVC Schedule
40 piping and fit-
tings are acceptable
material_
for the vent system on all 40
gallon and 50 gallon 40,000
BTU/HR
models.
3. It cannot be connected
to existing vent piping or chimney.
4. It must terminate
horizontally
to the outdoors.
NOTE: See page 20 for vertical venting
through
a roof.
17