Gas Piping - Kenmore 153.559400 Use & Care Manual

Table of Contents

Advertisement

SHE£_
M_TAL SCREWS
f,£e_# #_ovided)
tNS_ALL THE DRAFT
HOOD WITH
THE FOUR SCREWS
PROVIDED
FIGURE 17.
Failure to have required clearances between vent piping and
combustible surfaces will result in a fire hazard.
Be sure vent pipe is properly connected to prevent escape of
dangerous flue gases which could cause deadly asphyxiation.
Chemical vapor corrosion of the flue and vent system may occur
if air for combustion contains certain chemical vapors. Spray can
propellants,
cleaning solvents,
refrigerator and air conditioner
refrigerants,
swimming
pool chemicals,
calcium
and sodium
chloride,
waxes, bleach
and process chemicals
are typical
compounds which are potentially corrosive.
TO
CHIMNEY
FIGURE
18.
Obstructed or deteriorated
vent systems may present serious
health risk or asphyxiation.
The vent pipe from the water heater must be no tess than the
diameter of the draft hood outlet on the water heater and must
slope upward at least 1/4 inch per linear foot (21 mm per meter).
See Figure 18.
All vent gases must be completely vented to the outdoors of the
structure (dwelling).
Install only the draft hood provided with the
new water heater and no other draft hood.
Vent pipes must be secured at each joint with sheet metal screws.
There must be a minimum
of 6 inches (153 mm) clearance
between single wall vent pipe and any combustible
surface.
Fill and seal any clearance
between
single wall vent pipe
and combustible
surfaces with mortar mix, cement, or other
noncombustible
substance.
For other than single wall, follow
vent pipe manufacturer's
clearance specifications.
To ensure a
tight fit of the vent pipe in a brick chimney, seal around the vent
pipe with mortar mix cement.
Breathing
Hazard - Carbon
Monoxide
Gas
• Flue gases may escape if vent
pipe is not connected.
• Do not store corrosive chemicals
in vicinity of water heater.
• Chemical
corrosion of flue and
vent system can cause serious
injury or death.
• Contact
a qualified
installer
or
service agency.
Breathing carbon monoxide can cause brain damage
or death. Always read and understand instruction manual.
Gas Piping
Fire and Explosion
Hazard
Do not use water
heater
with
any
gas
other
than
the
gas
shown on the rating plate.
Excessive
pressure
to
gas
control valve can cause serious
injury or death.
Turn
off
gas
lines
during
installation.
Contact
qualified installer
or
service agency.
Make sure the gas supplied
is the same type listed on the
model rating plate.
The inlet gas pressure must not exceed
14 inch water column (3.5kPa) for natural and propane gas (L.E)
gas. The minimum inlet gas pressure listed on the rating plate
is for the purpose of input adjustment.
If the gas control valve
is subjected to pressures exceeding 1/2 pound per square inch
(3.5kPa), the damage to the gas control valve could result in a
fire or explosion from leaking gas.
If the main gas line shutoffserving
all gas appliances is used, also
turn "OFF" the gas at each appliance.
Leave all gas appliances
shut "OFF" until the water heater installation is complete.
A gas line of sufficient size must be run to the water heater.
Consult the current edition of National
Fuel Gas Code ANSI
Z223.1/NFPA
54 and your gas supplier concerning pipe size.
There must be:
• A readily accessible manual shut off valve in the gas supply
line serving the water heater.
• A sediment trap ahead of the gas control valve to help prevent
dirt and foreign materials from entering the gas control valve.
• Aflexible
gas connector or a ground joint union between the
shut off valve and control valve to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting the
water heater. Use a soapy water solution, not a match or open
flame. Rinse off soapy solution and wipe dry.
The minimum inlet gas pressure shown on the rating plate is that
which will permit firing at the rated input.
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

153.559500

Table of Contents