Concealed Duct Type
Wire connection
REQUIREMENT
• Connect the wires matching the terminal numbers.
Incorrect connection causes a trouble.
• Pass the wires through the bushing of wire connection
holes of the indoor unit.
• Keep a margin (Approx. 100mm) on a wire to hang
down the electrical control box at servicing or other
purpose.
• The low-voltage circuit is provided for the remote
controller. (Do not connect the high-voltage circuit)
• Before performing wiring work in the electrical
control box, remove the air filter and the cover of the
box (fixed with 2 screws).
• Tighten the screws of the terminal block firmly, and
fix the wires with the cord clamps attached to the
electrical control box. (Do not apply tension to the
connecting section of the terminal block.)
• Mount the cover of the electrical control box not to
pinch the wires.
Electrical
control box
Hole for wiring
Cover of the box
1
2
3
A
B
Remote
Connecting wire
controller wiring
Cord clamp
10
1
2
3
10
50
30
Earth line
Connecting wire
21-EN
Installation Manual
See the figure on the left for
connecting wires to the terminal
block.
Indoor/Outdoor connecting wire
Remote Controller Wiring
• Strip off approx. 9mm the wire to be connected.
Wiring diagram
Terminal block for
remote controller
Terminal block
wiring of indoor unit
Remote
A
A
controller
B
B
unit
Remote controller wire
(Locally procured)
Concealed Duct Type
– 11 –
8
Applicable
Controls
REQUIREMENT
When the air conditioner is used for the first time, it will
take some moments after the power has been turned on
before the remote controller becomes available for
operations: This is normal and is not indicative of trouble.
• Concerning the automatic addresses (The automatic
addresses are set up by performing operations on the
outdoor interface circuit board.)
While the automatic addresses are being set up, no
remote controller operations can be performed. Setup
takes up to 10 minutes (usually about 5 minutes).
• When the power is turned on after automatic address
setup
It takes up to 10 minutes (usually about 3 minutes) for
the outdoor unit to start operating after the power has
been turned on.
Before the air conditioner was shipped from the factory,
all units are set to [STANDARD] (factory default). If
necessary, change the indoor unit settings.
The settings are changed by operating the wired remote
controller.
* The settings cannot be changed using only a
wireless remote controller, simple remote controller
or group control remote controller by itself so install
a wired remote controller separately as well.
Installation Manual
Basic procedure for changing
settings
Change the settings while the air conditioner is not
working. (Stop the air conditioner before making
settings.)
CAUTION
Set only the CODE No. shown in the following table: Do
NOT set any other CODE No.
If a CODE No. not listed is set, it may not be possible to
operate the air conditioner or other trouble with the
product may result.
* The displays appearing during the setting process
differ from the ones for previous remote controllers
(AMT21E, AMT31E). (There are more CODE No.)
1
3
4
6
1
5
2
1
Push and hold
button and "TEMP."
button simultaneously for at least 4
seconds. After a while, the display flashes
as shown in the figure. Confirm that the
CODE No. is [01].
• If the CODE No. is not [01], push
button to
clear the display content, and repeat the
procedure from the beginning. (No operation of
the
remote controller is accepted for a while
after button is pushed.)
(While air conditioners are operated under the
group control, "ALL" is displayed first. When
is pushed, the indoor unit number
displayed following "ALL" is the header unit.)
(* Display content varies with the indoor unit
model.)