Toshiba RAV-SM564BT-E Installation Manual page 16

Indoor unit
Hide thumbs Also See for RAV-SM564BT-E:
Table of Contents

Advertisement

Concealed Duct Type
[Procedure example]
Manual address setup procedure
While the operation stops, change the setup.
(Stop the operation of the unit.)
7
3
3
-2,
-1,
4
4
-2,
-1,
5
5
-1,
-2
6
7
3
-3,
4
-3,
5
-3,
1
2,6
1
Push
+
+
buttons simultaneously
for 4 seconds or more. After a while, the
display part flashes as shown below. Check
the displayed CODE No. is [10].
When the CODE No. is other than [10], push
button to erase the display and repeat procedure
from the first step.
(After pushing
button, operation of the remote
controller is not accepted for approx. 1 minute.)
(For a group control, No. of the firstly displayed
indoor unit becomes the header unit.)
(* Display changes according to
the model No. of indoor unit.)
2
Every time
button is pushed, the
indoor UNIT No. in the group control is
displayed in order. Select the indoor unit of
which setup is changed.
In this time, the position of the indoor unit of which
setup is changed can be confirmed because fan of
the selected indoor unit operate.
29-EN
Installation Manual
3
1. Specify CODE No. [12] with TEMP.
/
buttons.
(CODE No. [12]: Line address)
2. Change the line address from [3] to [2] with TIME
/
buttons.
3. Push
button.
In this time, the setup finishes when the display
changes from flashing to lighting.
Indoor UNIT No. before setup change is displayed.
4
1. Specify CODE No. [13] with TEMP.
/
buttons.
(CODE No. [13]: Indoor address)
2. Change the indoor address from [3] to [2] TIME
/
buttons.
3. Push
button.
In this time, the setup finishes when the display
changes from flashing to lighting.
Indoor UNIT No. before setup change is displayed.
Concealed Duct Type
– 15 –
5
1. Specify CODE No. [14] TEMP.
/
(CODE No. [14]: Group address)
2. Change the SET DATA from [0001] to [0002] TIME
/
buttons.
(SET DATA [Header unit: 0001] [Follower unit:
0002])
3. Push
button.
In this time, the setup finishes when the display
changes from flashing to lighting.
Indoor UNIT No. before setup change is displayed.
6
If there is other indoor unit to be changed,
2
5
repeat procedure
to
to change the setup.
When the above setup has finished, push
to select the indoor UNIT No. before
change of setup, specify CODE No. [12], [13],
[14] in order with TEMP.
/
and then check the changed contents.
Address change check Before change:
[3-3-1] → After change: [2-2-2]
Pushing
button clears the contents of which
setup was changed.
2
(In this case, procedure from
is repeated.)
Indoor UNIT No. before setup change is displayed.
Installation Manual
7
After check of the changed contents, push
button. (Setup is determined.) When
buttons.
button is pushed, the display disappears
and the status becomes the usual stop
status. (When
button is pushed the
operation from the remote controller is not
accepted for approx. 1 minute.)
• If the operation from the remote controller is not
accepted even 1 minute or more passed after
pushing
button, it is considered that the
address setup is incorrect.
In this case, the automatic address must be
again set up.
Therefore repeat procedure of the setup
change from the Procedure
buttons,
1
.
30-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-sm804bt-eRav-sm1104bt-eRav-sm1404bt-e

Table of Contents