Item
Function
Capacity
Capacity
Total power input
Max. power input
EER or COP
Energy efficiency stage
Dehumidifying capacity
Power cable
Power source
Running /Max.Running current
Start Current
Fuse
Unit model (color)
Compressor
Fan
Heat exchanger
Dimension
Refrigerant control method
Defrosting
Noise level
material of reduce noise
crankcase heater power
Weight
Refrigerant
Pipe
Connecting Method
Between I.D &O.D
Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃DB
Outdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser
calibrated sound intensity meter. It is a sound pressure noise level.
Model / Manufacture
Type
Type × Number
Speed
Fan motor output power
Air-flow(H-M-L)
Type / Diameter
Total area
Temp. scope
External
(L×W×H)
Package
(L×W×H)
(Net / Shipping)
Type / Charge
Recharge quantity
Liquid
Gas
MAX.Drop
MAX.Piping length
>a__WcU[S^ <[c >a`V[e[a`Wc
Model
cooling
BTU/h
52000
W
15240
W
6000
W
8000
W/W
2.54
10‐³×m³/h
N, V, Hz
A / A
cooling: 10.0/13.5, heating: 10.0/13.5
A
A
r/min
kW
m³/h
mm
mm×mm×mm
mm×mm×mm
mm/mm
dB(A)
W
kg / kg
g
g/m
mm
mm
m
m
-20-
AU52NAIBEA
heating
65000
19050
6000
8000
3.18
E
D
6
H07RN-F 5G 4.0
3N~ 380V-400V 50HZ
50
3.15
AU52NAIBEA(WHITE)
C-SBN453H8A(SANYO)
scroll
Axial-flow×2
1050+30
0.25
8000
TP2M/9.52
0.92
43-60
948*340*1250
1050*440*1375
capillary
automatic
64/-/-
XPE
40
91/116
R407C 4000
65g/m
9.52
19.05
screw
30
50