Haier AU282AHBEA Service Manual page 194

Hide thumbs Also See for AU282AHBEA:
Table of Contents

Advertisement

Charging amount of refrigerant
When the total length (L) of the two indoor units' connecting pipe is less than 5m, it is unnecessary
to charge additional refrigerant.
If the connecting pipe (L) exceeds 5m, it shall charge Mg additional refrigerant per meter.
That is: Refrigerant charging amount = (L-5) x M (g)
For the unit with liquid pipe 6.35mm, M=30
For the unit with liquid pipe 9.52mm, M=65
Only in COOLING operation can charge the additional refrigerant.
When charging, the refrigerant shall be charged from the charging nozzle of low pressure vavle.
Be carefull when charging refrigerant, do not let the air mix into the system,and must charge
the additional refrigerant in liquid condition.
Electric wiring
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER
SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS.
GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING
LINE VOLTAGE CONNECTIONS.
(1) Selection of size of power supply and interconnecting wires.
Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped
terminal lugs with insulated grip on the ends of the wires.
Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with
less than 2% voltage drop.)
Item
Model
AU28NAHBEA
AU282AHBEA
AU242AHBEA
(2) Wiring connection
Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by
terminals.
For the detailed wiring connection with the indoor units, see the corresponding indoor
operation and instruction manual.
(3) Wiring procedure
1) Remove the screws on the side before taking off the front panel toward the direction shown in figure.
2) Connect wires to the terminal block correctly and fix the wires with a wire clamp equipped nearby the
terminal block.
3) Route the wires in a proper way and penetrate the wires through the opening for electric wiring on the
side plate.
WARNING
Circuit breaker
Switch breaker
Overcurrent protector
Phase
(A)
rated capacity (A)
30
3
40
1
>a__WcU[S^ <[c >a`V[e[a`Wc
Power source
wire size
(minimum)
2.5mm 2
20
4.0mm 2
26
-194-
Earth leakage breaker
Switch
Leak
breaker
current
30mA
30
40
30mA