Reference Calculations
Heating Calculations:
HE
LWT = EWT -
gpm x 500
HC
LAT = EAT +
cfm x 1.08
TH = HC + HW
Legend
Abbreviations and Definitions
cfm
= airflow, cubic feet/minute
EWT = entering water temperature, Fahrenheit
gpm
= water flow in gallons/minute
WPD = water pressure drop, psi and feet of water
EAT
= entering air temperature, Fahrenheit (dry bulb/wet bulb)
HC
= air heating capacity, MBtu/h
TC
= total cooling capacity, MBtu/h
SC
= sensible cooling capacity, MBtu/h
kW
= total power unit input, kilowatts
HR
= total heat of rejection, MBtu/h
HE
= total heat of extraction, MBtu/h
Cooling Calculations:
HR
LWT = EWT +
gpm x 500
SC
LAT (DB) = EAT (DB) -
cfm x 1.08
LC = TC - SC
SC
S/T =
TC
AFFINITY SINGLE & DUAL CAPACITY SERIES INSTALLATION MANUAL
HWC = hot water generator capacity, MBtu/h
EER
= Energy Efficient Ratio
= Btu output/Watt input
COP = Coefficient of Performance
= Btu output/Btu input
LWT
= leaving water temperature, °F
LAT
= leaving air temperature, °F
TH
= total heating capacity, MBtu/h
LC
= latent cooling capacity, MBtu/h
S/T
= sensible to total cooling ratio
39