Reference Calculations

Heating Calculations:
HE
LWT = EWT -
GPM x 500*
NOTE: * When using water. Use 485 for 15% methanol/water or Environol solution.
Legend
Abbreviations and Definitions
ELT
= entering load fluid temperature to heat pump
LLT
= leaving load fluid temperature from heat pump
LGPM = load flow in gallons per minute
LWPD = load heat exchanger water pressure drop
EST
= entering source fluid temperature to heat pump
LST
= leaving source fluid temperature from heat pump
SGPM = source flow in gallons per minute
SWPD = source heat exchanger water pressure drop
EER
= cooling energy effciency (TC/KW)
Cooling Calculations:
HR
LWT = EWT +
GPM x 500*
PSI
= pressure drop in pounds per square inch
FT HD = pressure drop in feet of head
KW
= kilowatt
HR
= heat rejected in MBTUH
TC
= total cooling capacity in MBTUH
COP
= coefficient of performance (HC/KW x 3.413)
HC
= heating capacity in MBTUH
HE
= heat of extraction in MBTUH
36