Open-Rack Batteries - Liebert 610 Series Installation Manual

100-225kva, 60hz, three phase multi-module
Hide thumbs Also See for 610 Series:
Table of Contents

Advertisement

5.4

Open-Rack Batteries

When batteries other than Liebert battery cabinets are used, a remote battery disconnect switch with
overcurrent protection is required per the National Electrical Code. Refer to Required Battery Discon-
nect Rating in the site planning data tables in Appendix A for recommended overcurrent protection
ratings. Contact your Liebert sales representative for more information.
1. Install battery racks/cabinets and batteries per manufacturer's installation and maintenance
instructions.
2. Verify battery area has adequate ventilation and battery operating temperature complies with
manufacturer's specification. Installations using vented lead-acid batteries MUST have adequate
ventilation to remove explosive gases per local and national codes.
3. Low voltage control wiring must be kept separate from power wiring and run in separate
conduits.
4. Ensure that battery racks are properly grounded according to code requirements in your area.
If you have any questions concerning batteries, battery racks or accessories, contact your local sales
representative or Liebert Global Services at 1-800-LIEBERT.
CAUTION
!
Cables between batteries and the UPS modules should be run in matched pairs,
positive-with-negative, within each conduit or cable run. Grouping like-polarity cables
together (i.e., positive-with-positive and negative-with-negative) can cause stress or damage
to the cables, conduit or buswork.
12
Battery Installation