Page 1
OWER ROTECTION Series 600T™ UPS Multi-Module Three Phase 500 kVA to 750 kVA, 60 Hz Installation Manual...
Page 2
FACTURER PRIOR TO MOVING A BATTERY CABINET. Battery cabinets contain non-spillable batteries. Keep units upright. Do not stack. Do not tilt. Failure to heed this warning could result in smoke, fire or electric hazard. Call 1-800-LIEBERT prior to moving battery cabinets.
Page 7
MPORTANT AFETY NSTRUCTIONS Save These Instructions. This manual contains important instructions that should be followed during installation of your Series 600T UPS and batteries. WARNING EXERCISE EXTREME CARE WHEN HANDLING UPS CABINETS TO AVOID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL. THE UPS MODULE WEIGHT RANGES UP TO 12,000 POUNDS (5,455 KG), INCLUDING INPUT TRANSFORMER.
Page 8
LOCATE CENTER OF GRAVITY SYMBOLS AND DETERMINE UNIT WEIGHT BEFORE HANDLING CABINET. If you require assistance for any reason, call the toll-free Liebert Global Services number; 1-800- 543-2378. For LGS to assist you expediently, please have the following information available: Part Numbers:...
A Note emphasizes important text. If the note is not followed, equipment could be damaged or may not operate properly. For example: NOTE If the UPS system has a blown fuse, the cause should be determined before you replace the fuse. Contact Liebert Global Services. Safety Precautions...
The batteries should not exceed 25°C (77°F). At elevations above 4,000 feet (1219 meters) derating may be required (consult your Liebert sales representative). 5. Even though your Liebert UPS unit is at least 93% efficient, the heat output is substantial. For more specific information, see Appendix A - Site Planning Data. Be sure environmental conditioning systems can accommodate this BTU load, even during utility outages.
1. SCCT is a stand-alone cabinet containing system control logic for up to six UPS modules, static bypass switch, manually operated disconnects for the static bypass switch, and two motor-operated system breakers. The SCCT is painted the same color as the Liebert UPS, but does not match the sheet metal style of the UPS.
NLOADING AND ANDLING The UPS module is shipped in one cabinet to allow easy handling at the site. Because the weight distribution in the cabinet is uneven, use extreme care during handling and transport. Your installation may also include Battery Cabinets and a System Control Cabinet. WARNING EXERCISE EXTREME CARE WHEN HANDLING UPS CABINETS TO AVOID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL.
Do not attempt to install the system if damage is apparent. If any damage is noted, file a damage claim with the shipping agency within 24 hours and contact Liebert Global Services at 1-800-543-2378 to inform them of the damage claim and the condition of the equipment.
QUIPMENT OCATION 1. Handle cabinet(s) in accordance with the Section 1.0 Safety Precautions and 3.0 Unloading & Handling. Use a suitable material handling device to move cabinet to its final location. Exercise extreme care because of the uneven weight distribution. Carefully lower the cabinet to the floor.
ATTERY NSTALLATION Battery Safety Precautions Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries. When replacing batteries, use the same number and type of batteries. CAUTION Lead-acid batteries contain hazardous materials.
Page 17
SANS AVOIR DETERMINE LES RAISONS DE LA DEFECTUOSITE, PEUT ENTRAINER DES BLESSURES OU DES DOMMAGES SERIEUX A L’EQUIPEMENT. POUR ASSISTANCE, APPELER LE DEPARTEMENT DE SERVICE A LA CLIENTELE DE LIEBERT. DANGER Les accumulateurs plomb-acide contiennent de la matière comportant un certain risque. Les accumulateurs doivent être manipulés, transportés et recyclés ou éliminés en accord avec les...
Page 18
Les accumulateurs plomb-acide présentent un risque d’incendie parce qu’ils génèrent des gaz à l’hydrogène. Les procédures suivantes devront être respectées. 1. NE PAS FUMER lorsque près des accumulateurs. 2. NE PAS produire de flammes ou d’étincelles près des accumulateurs. 3. Décharger toute électricité statique présente sur votre corps avant de toucher un accumulateur en touchant d’abord une surface métallique mise à...
2. Cabinet Inspection. Remove all panels and visually inspect the batteries, bus connections, and cabinet for any damage. Exercise caution; voltage is present within the Battery Cabinet even before installation. If there are signs of damage, do not proceed. Call Liebert Global Services at 1-800-543-2378.
UPS grounding require grounded-wye service. The UPS system requires a bypass neutral for sensing and monitoring the quality of the bypass input. If the building service is straight delta or corner-grounded delta, contact your Liebert representative for details of the Artificial Neutral or Isolated Neutral kits for the System Control Cabinet.
Preferred Grounding Configuration, 480 or 600 VAC Input and Output, Isolated Power Distribution Units, Wye-Connected Service Figure 3 Preferred Grounding Configuration, 480 or 600 VAC Input and Output The most-common configuration of Series 600T UPS Multi-Module Systems is with 480 VAC input, 480 VAC output, and a connected load consisting of multiple Power Distribution Units (PDUs) with isolation transformers in the PDUs to produce 208 VAC.
Grounding Configuration, 480 or 600 VAC Input and Output, Delta Source Figure 4 Grounding Configuration with Ungrounded Delta Source Input As previously mentioned, Series 600T UPS systems require a bypass input netrual for sensing and monitoring. With a wye-connected input source, the installer should always connect the building service neutral to the System Control Cabinet (SCC) output neutral to achieve this.
Preferred Grounding Configuration with Power-Tie Switchgear Figure 5 Preferred Grounding Configuration, Power-Tie Systems Multi-Module Systems can be used with Power-Tie switchgear to provide dual critical load busses. The Power-Tie switchgear permits transferring critical loads from one critical bus to the other so that one UPS system and associated breakers can be de-energized for maintenance.
Grounding Configurations, Battery Systems Figure 6 Battery Cabinet Grounding Configuration Large, open-rack battery systems are normally either locally grounded or left ungrounded, depending on local code requirements. Battery cabinet systems, on the other hand, should be grounded to the UPS module ground bus. The figure above illustrates how a simple one-cabinet system would be grounded.
IRING ONSIDERATIONS WARNING ALL POWER CONNECTIONS MUST BE COMPLETED BY A LICENSED ELECTRICIAN THAT IS EXPERIENCED IN WIRING THIS TYPE OF EQUIPMENT. WIRING MUST BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE NATIONAL AND LOCAL ELECTRICAL CODES. IMPROPER WIRING MAY CAUSE DAMAGE TO THE EQUIPMENT OR INJURY TO PERSONNEL.
Power Wiring 1. Power wiring must be run in individual, separate conduits or cable trays. Refer to the Outline and Terminal Details drawings (Figure 8 to Figure 15 and Figure 29 to Figure 32) for locations of the various power connections within the UPS and SCC. In particular, note the location of the rectifier input power connections.
Control Wiring Control wiring must be stranded and tinned and run in individual separate steel conduits. Con- trol wiring must be separated from power wiring. In addition, each control wiring cable group should be run in a separate conduit to minimize control signal interference. Refer to the Control Connection Locations and Control Wire Lists, Figure 33 through Figure 52.
(when needed). The battery disconnect (circuit breaker) requires a control cable. Liebert Battery Cabinets include power and control cables to join multi- ple cabinets together into a system. Additional (field-supplied) power or control wiring might be necessary to connect the battery cabinet system to the UPS.
Refer to the drawings in this manual and any other drawings provided by Liebert for this installa- tion. Make all of the following connections: 1. AC power cables from input power source circuit breaker (RIB) to UPS Module Input. Observe phase rotation.
Page 32
NOTE DC power and battery circuit breaker control cables are provided with some Liebert-brand Battery Cabinets. Power cables are sized for interconnecting Battery Cabinets. Field-supplied cabling might be required to connect Battery Cabinets to the UPS module, depending on cabinet configuration and layout.
10.0 W IRING NSPECTION 1. Verify all power connections are tight. 2. Verify all control wire terminations are tight. 3. Verify all power wires and connections have proper spacing between exposed surfaces, phase- to-phase and phase-to-ground. 4. Verify that all control wires are run in individual, separate, steel conduit. Table 1 Power Wiring Terminals - Factory Supplied UPS Module Rating...
Table 3 Table 310-16 Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts, 60° to 90°C (140° to 194°F) Not More than Three Conductors in Raceway or Cable or Earth (Directly Buried), based on Ambient Temperature of 30° (86°F) Size Temperature Rating of Conductor. See Table 310-13. Size 60°C 75°C...
12.0 A A - S PPENDIX LANNING 500-750kVA Multi-Module Systems 12.1 Notes 1. Nominal rectifier AC input current (considered continuous) is based on full rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current limit are defined in NEC 100.
Page 87
Table 4 Series 600T Multi-Module Systems, 500-750 kVA - 480 Volt Input Inverter Required Maximum Rectifier Battery Battery Maximum Floor Bypass Discon- Current Heat Dis- Dimen- Approx. Loading Input AC Output nect at End of sipation sions Weight Lb./ Rating Options Current Current...
Table 5 Series 600T Multi-Module Systems, 500-750 kVA - 600 Volt Input Inverter Required Maximum Rectifier Battery Battery Maximum Floor Bypass Discon- Current Heat Dis- Dimen- Approx. Loading Input AC Output nect at End of sipation sions Weight Lb./ Rating Options Current Current...
The Company Behind The Products With more than 500,000 installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics: •...