Liebert 1000kVA Operation & Maintenance Manual

Liebert 1000kVA Operation & Maintenance Manual

100-1000kva, 60hz three phase multi-module
Table of Contents

Advertisement

Quick Links

AC P
S
OWER
YSTEMS
S
610™ UPS
ERIES
O
& M
M
PERATION
AINTENANCE
ANUAL
100-1000kVA, 60Hz
Three Phase
Multi-Module

Advertisement

Table of Contents
loading

Summary of Contents for Liebert 1000kVA

  • Page 1 AC P OWER YSTEMS 610™ UPS ERIES & M PERATION AINTENANCE ANUAL 100-1000kVA, 60Hz Three Phase Multi-Module...
  • Page 2: Contacting Liebert For Support

    For repair or maintenance service outside the 48 contiguous United States, contact Liebert Global Services, if available in your area. For areas not covered by Liebert Global Services, the authorized distributor is responsible for providing qualified, factory-authorized service.
  • Page 3: Table Of Contents

    ATTERY ABINET RECAUTIONS ONTACTING IEBERT FOR MPORTANT AFETY NSTRUCTIONS ............2 NTRODUCTION System Description.
  • Page 4 Liebert Global Services ........
  • Page 5 Figure 1 Multi-Module UPS, 100-500kVA ........... . 2 Figure 2 Multi-Module UPS, 500-750kVA .
  • Page 6 Figure 50 Battery equalize screen ............62 Figure 51 SCC status and alarm message areas .
  • Page 7: Important Safety Instructions

    MPORTANT AFETY NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and mainte- nance of your Series 610 UPS and batteries. WARNING Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel.
  • Page 8: Introduction

    NTRODUCTION System Description The role of the parallel-redundant multi-module UPS system is to supply uninterruptible, clean power to the critical load. The UPS maintains a full-voltage, low-distortion output, even if the utility source power sags, becomes distorted or fails. If there is an outage of the source power, the UPS maintains power to the load until an alternate source of power is activated or until the original power source is restored.
  • Page 9: Figure 2 Multi-Module Ups, 500-750Kva

    System software allows the operator or Liebert Global Services to enter application specific informa- tion. Overload, overvoltage, battery discharge and shutdown limits can be set by the operator. In effect, UPS operations are tailored for each site.
  • Page 10: Reliability

    2 million hours. In addition, our Quality Assurance program is certified to the requirements of ISO 9001 standards. Liebert Large UPS systems are ETL listed to the requirements of UL 1778. All equipment and compo- nents are manufactured to applicable UL, NEC, NEMA, ANSI, IEEE and CSA standards and guide- lines.
  • Page 11: Safety Precautions

    Series 610 UPS provides easy-to-follow, prompted instructions on the industry’s largest operator dis- play screen. If you ever need help, call Liebert Global Services (24 hours a day at 1-800-LIEBERT). Your attention to proper installation, operation and periodic maintenance will ensure that your mission-critical oper- ations receive the best possible protection from electrical disturbances and outages.
  • Page 12: Recharge

    Overloads in critical systems may be caused by inrush currents during connected equipment start-up or by faults in the critical load or distribution network. The Liebert Series 610 UPS system can main- tain full output voltage regulation while sustaining the following overloads: •...
  • Page 13: Figure 4 Scc Controls And Display Screen With Example Of The Monitor/Mimic Screen

    Introduction Figure 4 SCC controls and display screen with example of the Monitor/Mimic screen © 1989-2003...
  • Page 14: Options

    1. Battery The batteries provide power in the event of a power outage. The Liebert UPS can use a variety of battery types, provided the battery plant is designed for the UPS DC voltage range and the load requirements of your application.
  • Page 15 6. Isolation Transformers An optional rectifier input isolation transformer is available in a matching transformer cabinet; this feature is standard in 1000kVA models. A bypass isolation transformer is also available. 7. Three Breaker Maintenance Bypass This switchboard provides make-before-break maintenance bypass. It includes: UPS Bypass Input Breaker (BIB), Maintenance Bypass Breaker (MBB) and Maintenance Isolation Breaker (MIB).
  • Page 16: Theory Of Operation

    UPS system to the bypass source. The SCC includes ports for communicating with external devices. Liebert Multi-Module Units do not require an SCC for load sharing. Automatic, parallel module load sharing is a function built into the modules themselves; however interconnection through the SCC enables the modules to share data for more precise control.
  • Page 17: Ups Module

    Figure 6 UPS module block diagram MULTI-MODULE UPS SYSTEM CONTROL POWER Utility Input Power 2.1.2 UPS Module The UPS module consists of module controls, a rectifier/charger, an inverter, protective devices and other accessories. Module Controls: The module control logic monitors performance of the UPS module. The UPS module status is displayed locally and is also sent to the System Control Cabinet.
  • Page 18: Detailed Component Descriptions

    Reporting to a local monitor the information requested from the local terminal. d. Reporting information to a Liebert SiteScan central monitoring system. e. Relaying selected alarm messages to a Liebert Remote Monitor Panel and to a separate terminal board for customer use.
  • Page 19: Rectifier/Charger

    The UPS module rectifier/charger consists of an input circuit breaker, AC current limiting circuit, battery equalize charge circuit, DC filter, battery charge current limiting circuit and bridge rectifiers. Optional items are an isolation transformer and a 12-pulse rectifier (these are standard on 1000kVA units).
  • Page 20: Battery Charging Circuit

    2.2.3 Battery Charging Circuit The UPS module charging circuit is capable of recharging the battery plant to 95% of full capacity within 10 times the discharge time. Recharging the last 5% takes longer because of characteristics inherent in the battery. DC ripple voltage is limited to less than 0.5% RMS to preserve battery life during long-term float charging while the UPS system is operating on utility source power.
  • Page 21: Inverter

    Theory of Operation 2.2.4 Inverter The inverter is a solid state device that converts the DC output of the rectifier/charger or the battery to AC power. Operation The inverter converts DC power—from either the battery or the rectifier/charger—into three pulse- width-modulated/six-step waveforms.
  • Page 22: Static Bypass

    2.2.5 Static Bypass A static bypass is an integral part of the UPS System Control Cabinet (SCC). Refer to Figure 7. The static bypass consists of two reverse-paralleled SCRs (silicon-controlled rectifiers) per phase and solid-state switching devices working in conjunction with the motor-operated System Bypass Breaker (SBB).
  • Page 23 Theory of Operation Static Switch Isolation The motor-operated system bypass circuit breaker (SBB), wired in parallel with the static switch, automatically closes in approximately 200 milliseconds after the load is transferred to the bypass power source, removing the static switch from the power flow. Also, if required for maintenance, the static switch can be isolated from the bypass line by opening (to the OFF position) the Static Switch Disconnects.
  • Page 24 Transfer and Retransfer Conditions 1. Automatic Transfers to Bypass Critical bus conditions that will initiate an automatic transfer of the critical load from the UPS system to the bypass source are: a. System Overload: overcurrent condition in excess of the overload rating of the System Control Cabinet (SCC).
  • Page 25: Redundant Mode

    6. Retransfer Inhibited A retransfer from the bypass source to the UPS system shall be inhibited if any of the following conditions exist: a. Manual (and Automatic) Retransfer Inhibitions: 1. UPS system-to-bypass voltage difference ( V) exceeds a predetermined percentage (normally 5%).
  • Page 26: Operation

    PERATION Display Screen and Operator Controls Each Liebert Series 610 UPS cabinet is equipped with a microprocessor-based Operator Control Panel and Display Screen and System Control Panel designed for convenient and reliable operation. The System Control Cabinet (SCC) performs different functions than the UPS modules. Each cabinet has the controls and displays required to operate and monitor its functions.
  • Page 27: Figure 8 Typical Operator Controls

    Figure 8 Typical operator controls 100kVA- 500kVA 1000kVA Table 1 Typical operator controls Item Description Input Circuit Breaker (CB1) Module Output Circuit Breaker (CB2) Operator Control Panel Control Disconnect (behind inner door) Interlock Button (on rear of Control Panel) This manually operated circuit breaker provides power to the UPS module rectifier. In 625-750kVA modules and some 500kVA modules, this breaker is located in the transformer cabinet.
  • Page 28: Figure 9 Operator Controls, Typical Scct System Control Cabinet

    Figure 9 Operator controls, typical SCCT System Control Cabinet Table 2 Typical SCCT System Control Cabinet operator controls Item Description UPS Output Circuit Breaker System Bypass Circuit Breaker Operator Control Panel Interlock Button (on rear of Control Panel) Close Bypass Switch (behind door) Bypass Reset Switch (behind door)
  • Page 29: Figure 10 Series 610 Ups And Scc Operator Control Panels

    Figure 10 Series 610 UPS and SCC operator control panels Numbers are used as keys to data in Table 3, below. Table 3 Series 610 UPS and SCC operator control panels Item Description (Location) Display Screen (SCC and modules) (SCC and modules) Down (SCC and modules) Select...
  • Page 30: Figure 11 Switches Behind Scc Control Panel Door

    Figure 11 Switches behind SCC control panel door Numbers are used as keys to data in Table 4, below. Table 4 Series 610 UPS and SCC operator control panels Item Description (Location) Interlock Button (on rear of Control Panel) Bypass Reset Switch (SW1, on Transfer Relay Board) Close Bypass Switch...
  • Page 31: Menu Tree Navigation

    Menu Tree Navigation The Operator Interface Display is a blue-background display with white text. The display is always on, but the backlight will remain lit for 15 minutes following any display activation. After 15 minutes, the backlight will go out and the display may appear very dim. To reactivate the backlight, push any key.
  • Page 32: Master Menu Screen

    (external to the UPS module) is open or the Control Power switch is OFF. If power is avail- able and a display is blank, contact Liebert Global Services (1-800-LIEBERT). Note that status infor- mation may be available at local and remote terminals. Use control touch pads at the SCC to manually transfer the critical load to the bypass line if the SCC display goes blank while load is on UPS (a very unlikely event).
  • Page 33 6 seconds. This enables the operator to immediately see the effects of load shedding on time remaining and to accurately assess his power resources. • Meter Calibration—This security access screen enables an authorized Liebert field-service engineer to adjust and calibrate the UPS metered functions. The operator can view, but should not change, any of the settings.
  • Page 34: Scc Monitor/Mimic Display Screen

    • Battery Test (MMU Only)—The optional battery test screen allows the operator to perform manual battery tests to determine the general condition of the battery system. The results of the last 10 tests are recorded in non-volatile storage and can be retrieved through the battery test results screen.
  • Page 35 Status/Alarm Message Areas The status/alarm message areas display vital information about the operation of the UPS system. During normal operation no alarm messages should be present. Changes in the status of the system and possible alarm conditions can be monitored. Both the status and the alarm messages are dis- played in reverse video (highlighted—light on dark).
  • Page 36: Module Monitor/Mimic Display Screen

    3.2.3 Module Monitor/Mimic Display Screen From module Master Menu move the highlighted cursor to MONITOR/MIMIC DISPLAY. Press the Select pad and the Monitor/Mimic screen is displayed. The Monitor/Mimic display screen is a simplified block diagram of the UPS module and power connec- tions.
  • Page 37 Alarm Messages The alarm message area displays vital information about the operation of the UPS system. During normal operation no alarm messages should be present. Alarm conditions can be monitored. The alarm messages are displayed in reverse video (highlighted— light on dark). To clear a latching alarm, you must also press the Alarm Reset pad after the alarm condition is corrected.
  • Page 38: Figure 16 Monitor/Mimic Display Example: Normal Power Flow

    Figure 16 Monitor/Mimic display example: Normal power flow BYPASS INPUT 480V 480V 480V 60.0 Hz UPS INPUT PWR 480V 480V 480V MOD 1 ON LINE MOD 2 ON LINE MOD 3 ON LINE UPS INPUT PWR 480V 480V 480V 350A 350A 350A BATTERY...
  • Page 39: Figure 17 Monitor/Mimic Display Example: Utility Fail

    Figure 17 Monitor/Mimic display example: Utility fail BYPASS INPUT 0 Hz UPS INPUT PWR MOD 1 ON LINE SUM ALM MOD 2 ON LINE SUM ALM MOD 3 ON LINE SUM ALM UPS INPUT PWR BATTERY VOLTS 480 AMPS 645 DISCHARG ©...
  • Page 40: Figure 18 Monitor/Mimic Display Example: Load On Bypass, Ups Modules On And Charging Battery

    Figure 18 Monitor/Mimic display example: Load on bypass, UPS modules on and charging battery BYPASS INPUT 480V 480V 480V 60.0 Hz UPS INPUT PWR 480V 480V 480V MOD 1 ON LINE MOD 2 ON LINE MOD 3 ON LINE UPS INPUT PWR 480V 480V 480V...
  • Page 41: Figure 19 Monitor/Mimic Display Example: Load On Ups, One Ups Module Off Line

    Figure 19 Monitor/Mimic display example: Load on UPS, one UPS module off line BYPASS INPUT 480V 480V 480V 60.0 Hz UPS INPUT PWR UPS INPUT PWR 380V 380V 380V 480V 480V 480V BATTERY MOD 1 ON LINE MOD 2 OFF LINE SUM ALM VOLTS 540 MOD 3 ON LINE AMPS 75 CHARG...
  • Page 42: Figure 20 Monitor/Mimic Display Example: Load On Bypass, All Ups Modules Off Line

    Figure 20 Monitor/Mimic Display example: Load on bypass, all UPS modules off line BYPASS INPUT 480V 480V 480V 60.0 Hz UPS INPUT PWR UPS INPUT PWR 380V 380V 380V 480V 480V 480V BATTERY MOD 1 OFF LINE SUM ALM MOD 2 OFF LINE SUM ALM VOLTS 540 MOD 3 OFF LINE SUM ALM AMPS 75 CHARG...
  • Page 43: Walk-In Display Screen

    After the critical load is transferred from the bypass line to the UPS modules, the Input Amps bars continue to indicate the percent of the design input current to the UPS module rectifier. If any Input Amps bar differs from the average bar length by more than 10%, call Liebert Global Services.
  • Page 44: Status Reports Screens

    3.2.5 Status Reports Screens Go to the Master Menu and move the highlighted cursor to STATUS REPORTS. Press the Select button and the Status Reports screen is displayed. The Status Report screen is divided into four submenu reports: PRESENT STATUS, EVENT HIS- TORY, HISTORY STATUS and SYSTEM STATUS.
  • Page 45: Figure 23 Present Status Report Screens, Scc (Above) And Module

    Figure 23 Present status report screens, SCC (above) and module PRESENT STATUS ORDER - 000000 **** ACTIVE ALARMS **** Batt Discharging OUTPUT VOLTS OUTPUT AMPS OUTPUT FREQUENCY LOAD KVA BYPASS VOLTS END OF REPORT PRESENT STATUS PRESENT STATUS ORDER - 000000 ORDER - 000000 **** ACTIVE ALARMS **** Batt Discharging **** ACTIVE ALARMS **** Batt Discharging...
  • Page 46: Figure 25 History Status Report Screens

    40 frames before the fault, the frame when the fault occurred and 23 frames after the fault. This 64-page report is a very useful diagnostic tool for the operator or Liebert Global Services. Use the Up and Down pads to view the screens.
  • Page 47: Table 5 Alarm Conditions That Freeze History Data Gathering

    Table 5 shows the alarm conditions that stop the History Status buffer from gathering data. Table 5 Alarm conditions that freeze history data gathering Alarm in SCC Alarm in Module Auto Transfer to Bypass DC Cap Fuse Blown Output Overvoltage DC Overvoltage Shutdown Output undervoltage Inverter Fault...
  • Page 48: Figure 26 Battery Cycle Monitor Screen

    System Status The System Status screen displays the module Total Operating Hours, Enable Backlight and the Bat- tery Cycle Monitor. Battery Cycle Monitor—Module Only Selecting the Battery Cycle Monitor gives you access to detailed information about the module’s most recent battery discharge events. Periodic review of this data can give a good indication of battery per- formance and expected life.
  • Page 49: Figure 27 Battery Cycle Monitoring Summary Screen

    The Summary screen (Figure 27) shows Total Number of Discharge Cycles, Accumulated Battery Time, Accumulated Battery Amp Hours, Accumulated Battery Kilowatt Hours and Battery Tempera- ture. During a battery discharge event, the screen changes to show information about the present dis- charge cycle.
  • Page 50: System Configuration Screens

    SCC to your site requirements. Some of the information displayed is factory-set and should only be changed by Liebert Global Services. Parameters that should be adjusted by the user include date, time, auto dial number and modem baud rate.
  • Page 51: Figure 30 Date Screen

    Date This is the system’s real-time date setting. The system control program sends to each module the date entered at the System Control Cabinet (SCC). You cannot change the system date from the control panel of a UPS module. Figure 30 Date screen UP : DOWN : SELECT :...
  • Page 52: Figure 31 Time Screen

    Time This is the system’s real-time clock. The system control program sends to each module the time entered at the System Control Cabinet (SCC). You cannot change the system time from the control panel of a UPS module. Figure 31 Time screen UP : INCREASE VALUE DOWN :...
  • Page 53: Figure 32 Auto Dial Setting Screen

    Auto Dial This is a feature that automatically dials (through a customer supplied PC-compatible modem) a pre- programmed telephone number (up to 12 digits) when specified alarm conditions occur within the UPS system. The connection for the modem is at the SCC. Automatic dial attempts to the first num- ber are made at periodic intervals for 30 minutes.
  • Page 54: Figure 33 Modem Baud Rate

    Modem Baud Rate This sets the transmission rate at which the system relays data to a terminal through the modem. Figure 33 Modem baud rate EXIT Enable Auto Dial ... YES Enable Communication Check... NO Modem Baud Rate ... 2400 Auto Dial Number...
  • Page 55: Figure 35 Scc System Options Screen

    To change the Maximum Auto-Retransfer Attempts parameter, do the following at the SCC: 1. From the System Configuration Screen, press the Up or Down pad to highlight Maximum Auto- Retransfer Attempts. 2. Press the Select pad. The screen above will appear. 3.
  • Page 56: Figure 37 Battery Test Screen-Mmu Only

    Figure 37 Battery test screen—MMU only EXIT Battery Test Results Start Battery Test Stop Battery Test Select Battery Type...15 min Figure 38 Battery test results screen End DC End DC Voltage Current Continuous Duty Static Switch (Optional) This option applies to SCC only. This feature requires installation of a Customer Alarm Interface board.
  • Page 57: Figure 39 Monitor/Mimic Display Example: Continuous Duty Static Switch

    Figure 39 Monitor/Mimic display example: Continuous Duty Static Switch BYPASS INPUT 480V 480V 480V 60.0Hz UPS INPUT PWR 480V 480V 480V MOD 1 ON LINE MOD 2 ON LINE MOD 3 ON LINE Remote Monitor The Remote Monitor Panel (optional) displays eight (8) alarms. These alarms are also available for customer use through a set of contacts on a separate terminal board.
  • Page 58: Alarm Limit Settings Screen

    Go to the Master Menu and move the highlighted cursor to LIMIT SETTINGS. Press the Select pad and the Limit Settings screen is displayed. The Alarm Limit Settings screen has Security Access to enable an authorized Liebert field-service engineer to adjust the UPS system alarm limit settings.
  • Page 59 Battery Rating (Modules Only): This setting is a battery discharge rating in kilowatts under par- tial load for an extended period, typically 60 minutes. The UPS uses the two battery shutdown voltage settings and the two battery discharge ratings in computing rated and calculated time remaining dur- ing a discharge event.
  • Page 60: Load Transfer Procedures Screen

    3.2.8 Load Transfer Procedures Screen Go to the SCC Master Menu and move the highlighted cursor to LOAD TRANSFER PROCE- DURES. Note that this screen is displayed at the System Control Cabinet but is not required at the UPS modules. Press the Select pad and the Load Transfer Procedures screen is displayed. The Load Transfer Procedures screen contains instructions to transfer the critical load between the UPS system and the bypass line.
  • Page 61: Start-Up Procedures Screen

    3.2.9 Start-Up Procedures Screen From the SCC Master Menu, move the highlighted cursor to START-UP PROCEDURES. Press the Select pad and the SCC Start-Up Procedures screen is displayed (Figure 42). This screen contains the steps you must follow to start-up the UPS system. The instructions are listed so you can review them prior to performing the start-up.
  • Page 62: 3.2.10 Shutdown Procedures Screen

    Figure 43 Module start- up procedures screens DOWN : NEXT PAGE SELECT : MASTER MENU Verify that the control power is applied to the system control cabinet (check the display on the system control cabinet). Wait approximately two (2) minutes before attempting any other action . Select "SYSTEM CONFIGURATION"...
  • Page 63: Figure 44 Scc Shutdown Procedures Screen

    Figure 44 SCC shutdown procedures screen If load is not already being supplied by the bypass line, select the "LOAD TRANSFER PROCEDURE" screen and follow the instructions to transfer the load to bypass. Go to the modules(s) and follow the module "SHUTDOWN PROCEDURES." Press the ALARM RESET button to clear alarms which are no longer active.
  • Page 64: Battery Time Screen (Module Only)

    To perform the shutdown procedure, transfer the critical load from the UPS system to the bypass line (at the SCC). Then trip open the UPS module output and battery circuit breaker (MBD) and manually open the UPS module input circuit breaker. The Control Power switch may be turned Off if required for maintenance procedures.
  • Page 65: Figure 47 Battery Time Screen (45-Minute Discharge)

    Values for Calculated Total Time and Calculated Time Remaining will appear on the screen approxi- mately two minutes after the beginning of the discharge event. Calculated Time Remaining also appears on the Present Status Report screen. Both Calculated Total Time and Calculated Time Remaining will be updated every six seconds, reflecting actual load changes and battery condition.
  • Page 66 • Dirty battery jar covers 3. If the battery plant has been thoroughly examined for proper maintenance and condition and the Calculated value is still less than 80% of Rated value, contact Liebert Global Services. The Series 610 records information about each discharge event. This data can be reviewed on the Bat- tery Cycle Monitor screen, as described in 3.2.5 - Status Reports Screens.
  • Page 67: 3.2.12 Meter Calibration Screen

    Select pad and the Meter Calibration screen is displayed. The Meter Calibration screen enables a Liebert field-service engineer to adjust the calibration of the UPS metered functions at each cabinet. Access to these settings is limited by the Security Access con- trol.
  • Page 68: 3.2.13 Battery Equalize Screen

    3.2.13 Battery Equalize Screen Go to the Master Menu and move the highlighted cursor to BATTERY EQUALIZE. Press the Select pad and the Battery Equalize screen is displayed. The Battery Equalize screen enables the operator to adjust the battery equalize time. It is also used to choose between auto and manual battery equalize recharging modes.
  • Page 69: 3.2.14 Alarm And Status Messages

    5. COM FAIL: The UPS module is not communicating with the SCC. This could mean loss of power to the UPS module controls, a disconnected cable or a control logic failure (detected by watchdog timer. Call Liebert Global Services if you require assistance. To resume communication after control power is restored, sequence display to Master Menu.
  • Page 70: Table 8 Abbreviations Used In Alarm Messages

    Load Block Messages Status messages in the Load Block indicate how many modules are in the system, how many modules are ON LINE and whether the system is operating in the redundant mode. The following status messages may appear in the load block. 1.
  • Page 71: Table 9 Alarm Messages - Meaning And Corrective Action

    Either the positive (+) or negative (-) DC bus is grounded. No transfer or shutdown occurs. D, L, S Contact Liebert Global Services at once. Do not attempt to locate or repair the fault. At least one DC capacitor fuse has opened. The UPS module is taken off- line and the input and battery circuit breakers trip open.
  • Page 72 Manually set the Static Switch Disconnects to ON (closed) if the static switch is disconnected. If the alarm conditions are automatically corrected, reset the alarm to clear it. Contact Liebert Global Services if the alarm stays on. The bypass power source voltage is not within specifications.
  • Page 73 The UPS output current has exceeded 175% of the rated full load or the overload capacity has been exceeded. The UPS module is taken off-line and shut down. Contact Liebert Global Services at once. Do not attempt to reset circuit breakers. Excessive reverse power flow from the critical bus into the UPS inverter has occurred, probably because of low inverter output voltage or a phase mismatch.
  • Page 74 The UPS module is taken off-line and is shut down. Contact Liebert Global Services at once. Do not attempt to reset the circuit breakers. The Emergency Module Off (or Emergency Power Off) switch has been...
  • Page 75: Table 10 Alarm Messages - Summary

    Table 10 Alarm messages - summary Alarm Message Input Fail DC Ground Fault DC Capacitor Fuse Blown Battery CB Open Battery Discharging Low Battery Warning Low Battery Shutdown DC Overvoltage Shutdown Load On Bypass Auto Transfer to Bypass Auto Retransfer Primed Manual Reset/Retransfer Static Switch Unable Bypass Not Available...
  • Page 76: 3.2.15 Communication Interfaces

    • Reporting through an SNMP interface to a building management or network management system • Selected alarm messages to a Liebert Remote Monitor Panel and to contact closures for customer All external communication devices, including the modem, are optional equipment. Connections to communication ports are made by wiring cables to terminal boards at the SCC.
  • Page 77 This information can also be sent via SNMP interface to a local network or building manage- ment system. If your site has SNMP communications, the optional Liebert SiteNet Integrator allows you to monitor the status of all the dry-contact outputs of the Series 610. The Integrator module monitors up to 10 digital inputs and two temperature/humidity sensors and can control two external devices with con- tact closure outputs.
  • Page 78: Table 11 Series 610 Terminal Commands

    Remote Monitor Panel The Liebert Remote Monitor Panel provides an LED indication of the following conditions: • Load On UPS • Load On Bypass • Battery Discharge • Low Battery Warning • Overload • Ambient Overtemp • System Summary Alarm •...
  • Page 79: Modes Of Operation

    An SCCT with three modules is shown. The same modes of opera- tion apply to all configurations of the Liebert Series 610 UPS multi-module system. Highlighted (thick) lines in the diagrams indicate power flow and power availability.
  • Page 80: Load On Bypass

    3.3.1 Load on Bypass Load on Bypass, with the UPS not available, is shown in Figure 52. The UPS system could be in this mode of operation during either initial start-up or UPS system shutdown and isolation for mainte- nance. NOTE When the critical load is being supplied power from the bypass line, it is exposed to utility power disturbances.
  • Page 81: Figure 53 Load On Bypass, Ups Available

    Figure 53 Load on bypass, UPS available Battery Battery Figure 54 Load on UPS, bypass available Battery Battery System Controls Battery (can accommodate up to 6 UPS modules) System Controls Battery (can accommodate up to 6 UPS modules) SKRU Output SCCT To Critical Load SCCT...
  • Page 82: Momentary Overloads

    3.3.3 Momentary Overloads An overload in the critical load will continue to be supplied by the UPS system if the overload condi- tion does not exceed the current versus time curve of overload capacity for either the SCC rating or for the number of modules on-line.
  • Page 83: Input Power Failure-Load On Battery

    The voltage limits for these alarms are displayed on the UPS module Alarm Limit Settings screen. These limits were selected for your installation by Liebert Global Services during initial start- The battery block in the UPS module Monitor/Mimic Display indicates Charge or Discharge and the current in Amperes.
  • Page 84: One Module Off-Line

    3.3.5 One Module Off-Line A multi-module UPS system can be supplied with a back-up (redundant) UPS module, which is the typical configuration. A redundant system includes one more module than the number required to supply the critical load. A redundant system operates in the redundant mode if all modules are ON LINE.
  • Page 85: Off Battery

    When the UPS system is operating with the module battery disconnect (MBD) circuit breaker(s) open, the critical load is not protected from loss of the utility source power. For battery maintenance on multi-module systems, Liebert recommends taking the module requiring maintenance off-line before beginning the work. This precaution will minimize disturbances on the system bus if input power fails during the maintenance work.
  • Page 86: Emergency Modules Off

    3.3.7 Emergency Modules Off The Local Emergency Modules Off (LEMO) mode is used to remove power from all UPS system com- ponents and the critical load will continue to be supplied through the bypass line. The Emergency Module Off control is a guarded pad on the SCC Control Panel (see Figure 10). Lift the cover and press the pad.
  • Page 87: Remote Emergency Power Off

    3.3.8 Remote Emergency Power Off The Remote Emergency Power Off (REPO) mode is used to remove all power from the critical load. The Remote Emergency Power Off control is a switch located remotely from the UPS system. It will normally be in the same room as the critical load equipment. This mode can also be initiated by an automatic contact closure in the same external circuit as the manually operated switch.
  • Page 88: System Shutdown

    Use the Shutdown Procedures screen when performing a manual System Shutdown. Refer to 3.4.5 - Shutdown Procedures. Refer to 3.3.10 - Maintenance Bypass. Before performing any maintenance on your Liebert Series 610 UPS System, observe ALL of the WARNINGS in 4.0 - Maintenance. WARNING Lethal voltages are present within this system even when it is not on or when power is not being supplied.
  • Page 89: Figure 62 Load On Maintenance Bypass, Two Breakers

    CAUTION Instructions for operating the Maintenance Bypass circuit breakers are on the Maintenance Bypass cabinet. Make sure you understand the proper sequence before operating any circuit breaker. Operating a Maintenance Bypass circuit breaker out of sequence could cut off power to the critical load.
  • Page 90: Manual Procedures

    Manual Procedures The Liebert Series 610 UPS system is designed to function while unattended by an operator. The sys- tem control logic at the System Control Cabinet (SCC) monitors the performance of the UPS system, the availability of power sources and the current required by the critical load.
  • Page 91 Step 1. Before you apply power to the UPS modules, determine the position of the following circuit breakers and switches: a. Bypass Input Breaker (BIB) - If this circuit breaker is closed, you may already have power to the critical load through the bypass line. If this breaker is closed, leave it closed. If it is open, leave it open until you are ready to energize the bypass line.
  • Page 92 Step 2. If the bypass line is not supplied to the SCC, the LCD screen will be blank. Energize the bypass line by operating the following controls: a. Close the Bypass Input Breaker (BIB). This breaker may be in your Maintenance Bypass cabinet.
  • Page 93: Figure 64 Scc Start-Up Procedures Screen

    e. If the UPS Bypass line is available, but not yet supplying power to the load, close the circuit breakers (external to the UPS) required to provide power to the critical load equipment. Follow the three steps shown below. CAUTION Be sure to operate Maintenance Bypass circuit breakers in the proper sequence.
  • Page 94: Ups Module Start-Up

    Select the Monitor/Mimic Display on the LCD. In the ALARM MESSAGES block (see Figure 15), the only alarm present should be Battery CB Open. If any other alarm messages are present, do not pro- ceed with the module start-up. Contact Liebert Global Services (LGS) for assistance. Operation...
  • Page 95: Figure 65 Module Start-Up Procedures Screen

    Each input amps bar should be within 25% of the average bar length. Call Liebert Global Services if you need help. The Input Amps bars should settle at 25% or less after the momentary inrush current has subsided.
  • Page 96 Alarm Reset pad to clear the Alarm Messages. Refer to Table 9 for an explanation of any remaining alarm messages. Call Liebert Global Services if you cannot clear the remaining alarm messages. If no alarm messages are displayed, the UPS module is now ready to provide filtered, uninterruptible power to the critical bus.
  • Page 97: Load Transfer Procedures

    Return to the Monitor/Mimic Display screen to monitor the operation of the UPS system. Press the Alarm Reset pad to clear any latched alarm messages removed by the new load status. Refer to Table 9 if an alarm message other than Load On Bypass is still displayed. Contact Liebert Global Services if you require assistance.
  • Page 98: Maintenance Bypass Load Transfers

    3.4.4 Maintenance Bypass Load Transfers To manually transfer the load between Maintenance Bypass and the UPS system bypass line, care- fully follow these instructions. Do not transfer the load between Maintenance Bypass and the UPS system (module inverters) output. Use the SCC Monitor/Mimic Display screen to verify the UPS sys- tem bypass line is available.
  • Page 99: Shutdown Procedures

    System Control Cabinet (SCC) when required for maintenance or if you need to perform maintenance on a UPS module in a non-redundant system. Before performing any maintenance on your Liebert Series 610 UPS, observe ALL of the WARN- INGS in 4.0 - Maintenance.
  • Page 100: Figure 68 Module Shutdown Procedures Screen

    Perform a Module Shutdown Procedure when you want to remove power from a UPS module when required for maintenance. Before performing any maintenance on your Liebert Series 610 UPS, observe ALL of the WARN- INGS in 4.0 - Maintenance. Use the module Monitor/Mimic Display to determine the operating condition of the UPS module.
  • Page 101: Automatic Operations

    You will still have power to the UPS controls, and you may have power to the static switch. Automatic Operations The Liebert Series 610 UPS system is designed to function while unattended by an operator. The sys- tem control logic monitors the performance of the UPS, the availability of power sources and the cur- rent required by the critical load.
  • Page 102: Overloads (Without Transfer)

    3.5.1 Overloads (Without Transfer) The UPS system is capable of sustaining full output voltage (±2% of the nominal voltage) for overload conditions that remain within (under) the current versus time curve of system overload capacity and the capacity of modules on-line (Figure 69). Note that the time scale is not linear. Load On UPS is illustrated in Figure 54.
  • Page 103: Automatic Retransfers To Ups

    3.5.3 Automatic Retransfers to UPS Automatic Retransfer to UPS is an option that you can select from the SCC System Configuration screen. If you do not want the UPS system to initiate any automatic retransfers, set Max Auto-Rexfer Attempts to zero (0). In an automatic retransfer, the two motorized circuit breakers (System Bypass and UPS Output) are both closed simultaneously for a short period of time (overlap).
  • Page 104: Maintenance

    Do not substitute parts except as authorized by Liebert Corporation. Maintain the UPS cabinets free of foreign materials such as solder, wire cuttings, etc. Contact Liebert Global Services if you are not sure of the procedures to follow or if you are not familiar with the circuitry.
  • Page 105: Liebert Global Services

    UPS, with or without scheduled preventive maintenance visits. Other sites can benefit from a variety of money-saving options. As a rule of thumb, Liebert recommends two preventive maintenance visits per year for the UPS. The first can be conducted with the UPS operational and includes an infrared scan of key UPS compo- nents.
  • Page 106: Routine Maintenance

    You are encouraged to become thoroughly familiar with the equipment, but at no time should you go beyond the specific procedures in this manual while performing maintenance or correcting a malfunc- tion. If you have any doubt as to what must be done, call Liebert Global Services at 1-800-LIEBERT for further instructions.
  • Page 107: Limited Life Components

    4.3.3 Limited Life Components Your Liebert UPS has a design life well in excess of 10 years. Well-maintained units can continue to provide economic benefits for 20 years or more. Long-life components are used in your UPS wherever practical and cost-effective. However, due to current component material and manufacturing technol- ogy limitations, a few components in your Liebert UPS will wear out and require replacement in less than 10 years.
  • Page 108: Battery Maintenance

    DC fuses operate at the rated battery voltage at all times. A blown DC bus fuse indicates a serious problem. Serious injury or damage to the equipment can result if the fuse is replaced without knowing why it failed. Call Liebert Global Services for assistance. 4.4.1...
  • Page 109 Ne jamais installer de batteries avec des cellules fissurées ou endommagées. Contacter Liebert Global Services ou le représentant agréé Liebert local. Une batterie peut poser un risque de choc électrique et de courant élevé provoqué par un court-circuit. Respecter les précautions suivantes lors de travaux sur les batteries: •...
  • Page 110 Compare these values with those shown below. The recorded nominal voltage should be no less than the value shown, while the recorded float voltage should be within the range shown. If a discrepancy is found, contact Liebert Global Services. Number of Cells Power Connections: Check for corrosion and connection integrity.
  • Page 111: Table 13 Battery Retorque Values

    HX400 HX500 If you have a different model battery, contact Liebert Global Services for the required torque value. To access battery cell terminals, disconnect the inter-tier cable and two shelf retaining screws. Once disconnected, insulate (with protective boot or electrical tape) the cables to prevent accidental shorts.
  • Page 112: Torque Requirements

    • Tracing a problem to a particular section is facilitated by alarm messages and the metered parameter indications. These are stored in the Status Reports and can be displayed at the Opera- tor Control Panel or at an optional terminal. A Liebert Global Services engineer will be familiar with test points inside the unit.
  • Page 113: Reporting A Problem

    Liebert service representative’s office nearest you. This information can be downloaded to Liebert Global Services by using the optional modem. Contact Liebert Global Services at 1-800-LIEBERT to report a problem or to request assistance.
  • Page 114: Specifications

    For loads with power factors below 0.7 lagging or with leading power factors, the UPS output is kVA limited and the UPS System may not meet all of its output performance specifications. Contact Lie- bert Global Services at 1-800-LIEBERT to request assistance for these applications. Figure 70 Output power envelope for 0.8 and 0.9 pf rated units...
  • Page 115: Environmental Conditions

    Derating for Higher 93% at 55°C Ambient Temperatures (see Note 3) Consult your Liebert sales representative regarding applications in high ambient temperatures or call 1-800-LIEBERT. Special temperature sensors must be installed at the factory. Derating for Higher Elevations (see Note 4) NOTES 1.
  • Page 116: Adjustments

    • Output Voltage: Nominal - operator adjustable ±5% • Line Drop Compensation: 0 to +5% - set at start-up to match load characteristics; if significant additional loads are connected, call Liebert Global Services Battery Operation The separate battery manufacturer’s manual, available on the manufacturer’s Web site, provides the necessary information for the installation, operation and maintenance of the battery.
  • Page 117: Electrical Specifications

    Fault Clearing Standard voltages for 100 - 450kVA units: 208, 480 and 600VAC Standard voltages for 500 - 1000kVA units: 480 and 600VAC Other voltages available on request. 3-phase, 3-wire plus ground. +10%, 15% (no battery discharge at...
  • Page 118 Specifications...
  • Page 120 © 2005 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.

This manual is also suitable for:

Series 610

Table of Contents