Input/Output Phase Loss Protection Selection (Pr. 251, Pr. 872) - Mitsubishi Electric FR-F720-00046 Instruction Manual

F700 series
Hide thumbs Also See for FR-F720-00046:
Table of Contents

Advertisement

Operation setting at fault occurrence

4.13.3 Input/output phase loss protection selection (Pr. 251, Pr. 872)

You can disable the output phase loss protection function that stops the inverter output if one phase of the
inverter output side (load side) three phases (U, V, W) is lost.
The input phase loss protection selection of the inverter input side (R/L1, S/L2, T/L3) can be valid.
Parameter
Number
Output phase loss protection
251
selection
Input phase loss protection
872
selection
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 179)
(1) Output phase loss protection selection (Pr. 251)
When Pr. 251 is set to "0", output phase loss protection (E.LF) becomes invalid.
(2) Input phase loss protection selection (Pr. 872)
⋅ When Pr. 872 is set to "1", input phase loss protection (E.ILF) is provided if a phase loss of one phase among the
three phases is detected for 1s continuously.
REMARKS
If input phase is lost when Pr. 872 = "1" (with input phase loss protection) and Pr. 261 ≠ "0" (power failure stop function valid),
input phase loss protection (E.ILF) is not provided but power-failure deceleration is made.
CAUTION
⋅ When an input phase loss occurs in the R/L1 and S/L2 phases, input phase loss protection is not provided but the inverter
output is shut off.
⋅ If an input phase loss continues for a long time, the converter section and capacitor lives of the inverter will be shorter.
♦ Parameters referred to ♦
Pr. 261 Power failure stop selection
152
Name
Initial Value
Refer to page 146
Setting Range
0
1
1
0
0
1
Description
Without output phase loss protection
With output phase loss protection
Without input phase loss protection
With input phase loss protection

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents