Mitsubishi Electric FR-F720-00046 Instruction Manual page 142

F700 series
Hide thumbs Also See for FR-F720-00046:
Table of Contents

Advertisement

Types of Monitor
Increments
Running speed
1(r/min)
Converter output
0.1V
voltage
Regenerative
0.1%
brake duty
Electronic thermal
relay function load
0.1%
factor
Output current
0.01A/0.1A
peak value
*5
Converter output
0.1V
voltage peak value
0.01kW/
Input power
0.1kW
0.01kW/
Output power
0.1kW
Load meter
0.1%
Cumulative
1h
energization time
*2
Reference voltage
output
Actual operation
1h
time 
*2*3
Motor load factor
0.1%
Cumulative power
0.01kWh/
0.1kWh
*6
*4, *5
Power saving
effect
Variable
according
to
Cumulative saving
parameters
power
*6
PID set point
0.1%
PID measured
0.1%
value
PID deviation
0.1%
Input terminal
status
Output terminal
status
Pr. 52 Parameter
Pr. 54 (CA)
Setting Value
Pr. 158 (AM)
Parameter
PU main
Setting
DU LED
monitor
Value
6
*1
8
*1
9
*1
10
*1
11
*1
12
*1
13
*1
*5
14
*1
*5
17
20
23
24
25
50
51
52
53
54
*1
55
*1
Monitor display and monitor output signal
Full-scale
value of the
terminal CA
and AM
The value
Displays the motor speed (The display
converted with
6
differs depending on the Pr. 37 and Pr. 144
the Pr. 37 value
settings.) (For details, refer to page 131 .)
from Pr. 55
200V class:
400V
8
Displays the DC bus voltage value
400V class:
800V
Brake duty set in Pr. 30 and Pr. 70 (Setting
9
Pr. 70
can be made for the FR-F720-03160 (FR-
F740-01800) or more)
Displays the motor thermal cumulative
10
100%
value on the assumption that the thermal
operation level is 100%.
Retains the peak value of the output
11
Pr. 56
current monitor and displays (clears at
every start)
200V class:
Retains the peak value of the DC bus
400V
12
voltage value and displays (clears at every
400V class:
start)
800V
Rated inverter
13
Displays power of the inverter input side
×
power
2
Rated inverter
14
Displays power of the inverter output side
×
power
2
Displays the torque current in % on the
17
100%
assumption that the Pr. 56 setting is 100%
Displays the cumulative energization time
since the inverter shipment
×
You can check the numbers of the monitor
value exceeded 65535h with Pr. 563.
Terminal CA: 20mA is output
21
Terminal AM: 10V is output
Displays the cumulative inverter running
time.
You can check the numbers of the monitor
×
value exceeded 65535h with Pr. 564.
Use Pr. 171 to clear the value.
(Refer to page 136 .)
Displays the output current value in % on
the assumption that the rated inverter
current value is 100%.
24
200%
Monitor value = output current monitor
value/rated inverter current
Displays the cumulative power amount
according to the output power monitor
×
Use Pr. 170 to clear the value.
(Refer to page 136.)
Inverter
Displays energy saving effect monitor
50
capacity
You can change the monitor to power
saving, power saving average value,
charge display and % display using
×
parameters.
(For details, refer to page 155.)
100%/
52
C42 or C44
Displays the set point, measured value and
100%/
deviation during PID control
53
C42 or C44
(For details, refer to page 232.)
×
Displays ON/OFF status of the input
×
terminal on the PU
(Refer to page 135 for DU display)
Displays ON/OFF status of the output
×
terminal on the PU
(Refer to page 135 for DU display)
Description
×
100 [%]
133
4

Hide quick links:

Advertisement

Table of Contents