Deciding on Where to Install the Air Conditioner
◆ RJ050F2HX **
Indoor unit
Outdoor unit
** 020/023/026/
035/052
RJ050F2HX **
07/09/12/18 **
※ RJ050F2HX ** Outdoor unit cannot be connected to the following indoor unit combination.
- MH052FMEA/MH052FUEA
100 mm
or more
CAUTION
3 m as minimum pipe length: It will reduce noise and
vibration.
300 mm
minimum
600 mm
minimum
※ The appearance of the unit may be different from the diagram depending on the model.
◆ Piping length and the helght
Dimension
Composition
※ The appearance of the unit may be different from the diagram depending on the model.
6
Power supply 0, V, Hz
1,220-240,50/60
200 mm
or more
600 mm
minimum
300 mm
minimum
1 Room max
2 Room total max
length
length
20m
A,B
Make at least one round:
It will reduce noise and vibration
◆ Piping outside diameter
Unit
** 020/023/026/
030/035/07/09/12 **
** 052/18 **
160 mm
or more
A
Max height between
indoor unit & outdoor unit
30m
15m
A+B
(H)
Outside diameter
Liquid
Gas
3/8"
1/4"
1/2"
B
Main power switch
Max height between
indoor units
7.5m
(h)
(h)
(H)