Connecting the cables to the outdoor unit
◆ RJ040F2HX ** /RJ050F2HX **
A-unit
1(L)
2(N)
1
2
Earth
terminal
B
1
2
Earth
terminal
L
N
Power cable to indoor units
A
Cable Type : A
B
Cable Type : B
C
Cable Type : C
The specification for cables :
Main Power Supply
Cable
Model
Specication
3G, 2.5mm² or
RJ040F2HX **
more,
RJ050F2HX **
H07RN-F
≫ Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to the power supply, it must be incorporated
in a wire with a contact opening of ≥3mm.
The terminal is connected too firmly , the terminal may be damaged.
Indoor unit
F1
F2
F1 F2
Assembly cable
C
F1 F2
Outdoor unit
L
N
2
1
A
Screw
M4
Indoor Power Supply
Cable
Type
Specication
3G, 1.0mm²or
A
more,
H07RN-F
B-unit
1(L)
2(N)
1
2
B
1
2
Earth
terminal
Main Power
Supply cable
Earth
terminal
Torque(kgf . cm)
Unfasten Torque
Tighten Torque
17~30
Communication Cable
Type
Specication
Type
2G, 0.75mm² or
B
C
more,
H07RN-F
F1
F2
F1 F2
Earth
terminal
C
F1 F2
F1 F2
B
A
Communication cable
to indoor units
Position
25~40
1(L),2(L),L,N,F1,F2
ELB
MCCB
20A
20A
13