(4) Utilizing or changing offline auto tuning
data for use
A700
<Operating procedure>
1) Perform auto tuning.
2) Set the following value in [Pr. 71]
Motor
SF-JR, SF-TH
Mitsubishi standard
SF-JR 4P 1.5kW or less
motor
Mitsubishi high
SF-HR
efficiency motor
Others
SF-JRCA 4P, SF-TH
(constant torque)
Mitsubishi constant-
SF-HRCA
torque motor
Others
(SF-JRC etc.)
SF-V5RU (1500r/min series)
SF-THY
Vector control
dedicated motor
SF-V5RU (except for
1500r/min series)
Other manufacturer's
standard motor
Other manufacturer's
constant-torque
motor
.
* Available only for
A700
3) In the parameter setting mode, read the following
parameters and set desired values. Mitsubishi
motor constants are used when 9999 is set in [Pr.
82, Pr. 90 to Pr. 94, Pr. 859].
[Pr. ]
Name
Motor excitation
82
current
90
Motor constant R1
91
Motor constant R2
92
Motor constant L1
93
Motor constant L2
94
Motor constant x
859
Torque current
Constants measured by offline auto tuning are used
when [Pr. 71 = 3, 13, 23, 33, 43, 53] are set. Constants
measured by offline auto tuning is overwritten when
the motor constants are changed after the [Pr. 71] is
set to "4,14,24,34,44,54"
As the motor constants measured in the offline auto
tuning have been converted into internal data (****),
refer to the following setting example when making
setting:
Setting example: To slightly increase [Pr. 90] value (5%)
When [Pr. 90 = 2516] is displayed, set
2516
2642].
(The
converted into a value for internal use.
Hence, simple addition of a given
value to the displayed value has no
significance.)
E700
[Pr. 71]
Setting
4
24
44
4
14
54
14
34 *
14
4
14
Setting
Incre-
Range
ments
0 to ****, 9999
1
0 to ****, 9999
1
0 to ****, 9999
1
0 to ****, 9999
1
0 to ****, 9999
1
0 to ****, 9999
1
0 to ****, 9999
1
1.05 = 2641.8, i.e. [Pr. 90 =
value
displayed
has
In
A700
changed by setting [Pr. 684 Tuning data unit switchover].
Note that tuning data can not be changed when [Pr.
684 = 1].
[Pr. ]
82
90
91
92
93
94
859
(5) Setting
A700
When setting the motor constants without using
offline auto tuning data, the [Pr. 92, Pr. 93] motor
constants may either be entered in [
Before starting operation, confirm which motor
constant unit is used.
To enter the [Pr. 92, Pr. 93] motor constants in [
<Operating procedure>
1) Set the following value in [Pr. 71]. If "star connection"
is mistaken for "delta connection" or vice versa during
setting of [Pr. 71], General-purpose magnetic flux
vector control, Advanced magnetic flux vector control,
Real sensorless vector control, and vector control
cannot be performed properly.
[Pr. 71]
Setting
* When [Pr. 71 = 7, 8, 17, 18] in
the motor constants directly, offline auto tuning
can be performed.
2) In the parameter setting mode, read the following
parameters and set desired values. Mitsubishi
motor constants are used when 9999 is set in [Pr.
82, Pr. 90 to Pr. 94, Pr. 859]. Use the following
formula to find [Pr. 859 Torque current].
Iq =
been
274
, display unit of motor constants can be
Setting Increments
[Pr. 684 = 0]
1
(internal data
converted
value)
the
motor
constants
E700
Star
Connection
Motor
Standard motor
5(7)
Constant-torque
15(17)
motor
Iq: Torque current
2
2
-
I
I
100
0
I
100
I
: No load current
0
PARAMETER
[Pr. 684 = 1]
55K or
75K or
less
more
0.01A
0.1A
0.001Ω
0.01mΩ
0.001Ω
0.01mΩ
0.1mH
0.01mH
0.1mH
0.01mH
0.1%
0.01%
0.01A
0.1A
directly
] or in [mH].
]
Delta
Connection
Motor
6(8)
16(18)
, after setting
A700
: Rated current