Electrode Setting; Turbulator Setting; Oil Line Connections - Riello 40 F10 Installation & Operating Manual

Single stage operation oil burner with manual air shutter
Table of Contents

Advertisement

IMPORTANT:
THESE DIMENSIONS MUST BE OBSERVED AND VERIFIED.
A) Loosen NUT (1), then turn SCREW
(2) until the INDEX MARKER (3) is
aligned with the correct index number
as per the Burner Set-up chart, on
page 12.
B) Retighten the RETAINING NUT (1).
NOTE: Zero and five are scale indica-
tors only. From left to right, the first line
is 5 and the last line 0.
This burner is shipped with the oil pump set to operate on a single line system.
To operate on a two line system the by-pass plug must be installed.
Warning: Do not operate a single line system with the by-pass plug installed.
Operating a single line system with the by-pass plug installed will result in damage
to the pump shaft seal.
Note: Pump pressure must be set at time of burner start-up. A pressure gauge is
attached to the PRESSURE PORT (8) for pressure readings. Two PIPE
CONNECTORS (5) are supplied with the burner for connection to either a single or a
two-pipe system. Also supplied are two ADAPTORS (3), two female 1/4" NPT, to adapt
oil lines to burner pipe connectors. All pump port threads are British Parallel Thread
design. Direct connection of NPT threads to the pump will damage the pump body.

ELECTRODE SETTING

5/32" or 4 mm
5/32" to 13/64" or 4 to 5 mm
D6003

TURBULATOR SETTING

OIL LINE CONNECTIONS

F10 - 8
3
2
1
D5997