6) Copy mode
By using the operation panel (FR-DU04), the parameter values can be copied to another inverter (only the
FR-A500 series).
1) Operation procedure
After reading the parameter values from the copy source inverter, connect the operation panel to the
copy destination inverter, and write the parameter values.
After writing the parameters to the inverter of copy destination, always reset the inverter, e.g. switch
power off once, before starting operation.
z
Parameter setting mode
FR-DU04
CONTROL PANEL
Hz
A
V
MON
EXT
PU
REV
FWD
FR-DU04
CONTROL PANEL
Hz
SET
A
V
MON
EXT
PU
REV
FWD
Press for
1.5 sec.
Note: 1. While the copy function is being activated, the monitor display flickers. The display returns to the
lit-up state on completion of the copy function.
2. If a read error occurs during parameter read, "read error (E.rE1)" is displayed.
3. If a write error occurs during parameter write, "write error (E.rE2)" is displayed.
4. If a data discrepancy occurs during parameter verify, the corresponding parameter number and
"verify error (E.rE3)" are displayed alternately. If the direct frequency setting or jog frequency
setting is discrepant, "verify error (E.rE3)" flickers. To ignore this display and continue verify,
press the [SET] key.
5. When the copy destination inverter is not the FR-A500 series, "model error (E.rE4)" is displayed.
Reference:
It is recommended to read the parameter values after completion of parameter setting.
By writing the parameter values from the operation panel fitted to a new inverter after inverter
replacement, parameter setup can be completed.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
FR-DU04
CONTROL PANEL
Hz
A
V
MON
EXT
PU
REV
FWD
FR-DU04
FR-DU04
CONTROL PANEL
Hz
A
V
MON
EXT
PU
MON
REV
FWD
Press for
(Note 1)
SET
SET
1.5 sec.
FR-DU04
FR-DU04
CONTROL PANEL
Hz
A
V
MON
EXT
PU
MON
REV
FWD
z
z
Parameter read
Parameter write
After writing the parameters,
always reset the inverter before
operation.
Connect to copy destination inverter.
51
OPERATION
FR-DU04
CONTROL PANEL
CONTROL PANEL
Hz
A
V
EXT
PU
MON
EXT
REV
FWD
REV
FWD
Press for
(Note 1)
(Note 1)
SET
1.5 sec.
FR-DU04
CONTROL PANEL
CONTROL PANEL
Hz
A
V
EXT
PU
MON
EXT
REV
FWD
REV
FWD
z
Parameter verify
Hz
A
V
PU
Hz
A
V
PU